<strong>Basic</strong> <strong>Rooftop</strong> Controller<br />
www.prolon.net<br />
2.1.6 Limits<br />
2.1.6.1 Return Air Temperature<br />
Figure 2.1.10: Limits configuration screen<br />
This section describes all the limits applicable to the return air temperature. If no return<br />
air temperature sensor is used, then these conditions are assumed to be satisfied.<br />
• Stop Cooling (1st Stage) when lower than:<br />
Units MIN MAX Default<br />
°C 10 40 14<br />
°F 50 104 57.2<br />
Re-enabled at 2°C (3.6°F) above this value.<br />
• Stop Cooling (2nd Stage) when lower than:<br />
Units MIN MAX Default<br />
°C 10 40 20<br />
°F 50 104 68<br />
Re-enabled at 2°C (3.6°F) above this value.<br />
• Stop Heating when higher than:<br />
Units MIN MAX Default<br />
°C 0 50 35<br />
°F 32 122 95<br />