<strong>Basic</strong> <strong>Rooftop</strong> Controller<br />

www.prolon.net<br />

2.1.6 Limits<br />

2.1.6.1 Return Air Temperature<br />

Figure 2.1.10: Limits configuration screen<br />

This section describes all the limits applicable to the return air temperature. If no return<br />

air temperature sensor is used, then these conditions are assumed to be satisfied.<br />

• Stop Cooling (1st Stage) when lower than:<br />

Units MIN MAX Default<br />

°C 10 40 14<br />

°F 50 104 57.2<br />

Re-enabled at 2°C (3.6°F) above this value.<br />

• Stop Cooling (2nd Stage) when lower than:<br />

Units MIN MAX Default<br />

°C 10 40 20<br />

°F 50 104 68<br />

Re-enabled at 2°C (3.6°F) above this value.<br />

• Stop Heating when higher than:<br />

Units MIN MAX Default<br />

°C 0 50 35<br />

°F 32 122 95<br />

24<br />