<strong>Basic</strong> <strong>Rooftop</strong> Controller<br />

www.prolon.net<br />

one. There will be a delay between each stage deactivation, which is equal to the<br />

minimum compressor off time.<br />

Units MIN MAX Default<br />

°C -40 40 9<br />

°F -40 104 48.2<br />

Re-enabled at 3°C (5.4°F) above this value.<br />

• Modulating heat limit of Analog Output 1: If Analog Output 1 is configured as<br />

modulating, it will decrease its signal to keep the supply temperature from exceeding<br />

this value.<br />

Units MIN MAX Default<br />

°C 21.5 55 40<br />

°F 70.7 131 104<br />

• Stop heating when higher than: All heating stages will shut off if the supply<br />

temperature exceeds this value.<br />

Units MIN MAX Default<br />

°C 21.5 55 50<br />

°F 70.7 131 122<br />

Re-enabled at 5°C (9°F) below this value.<br />

• Stop Fan if lower than: When the supply air temperature goes below this value, the fan<br />

will stop. This limit is ignored for a 5-minute period following a transition of the fan<br />

status from OFF to ON, unless it was first caused to stop by this limit.<br />

Units MIN MAX Default<br />

°C 0 21 4<br />

°F 32 69.8 39.2<br />

• Restart Fan at: If the fan has been stopped due to the supply low temperature limit<br />

(see previous limit), this is the temperature at which the fan will restart.<br />

Units MIN MAX Default<br />

°C 2+Stop Setpoint 20+Stop Setpoint 8+Stop Setpoint<br />

°F 3.6+Stop Setpoint 36+Stop Setpoint 14.4+Stop Setpoint<br />

26<br />