<strong>Basic</strong> <strong>Rooftop</strong> Controller<br />
www.prolon.net<br />
• Differential: The differential used for the Analog Output 1 heating stage. Only enabled<br />
if the Analog Output 1 Function is set to “Heating ONLY”.<br />
Units MIN MAX Default<br />
% 8 99 N/A<br />
• Enable Pulsing: Analog Output 1 will use pulse width modulation with a pulse width<br />
period of 1 second. Only enabled if using proportional. Pulse width modulation is<br />
designed for solid-state relay-equipped electric duct heaters.<br />
• Enable Reverse Acting: The output voltage will be inversely proportional to the<br />
calculated output value<br />
2.1.5.3 Preheating<br />
Preheating is calculated using a PI control loop (proportional and integral) to achieve the<br />
desired setpoint.<br />
• Setpoint: The setpoint used for the Analog Output 1 preheating control sequence. The<br />
Master Controller maintains the supply air at this value. Disabled if the Analog Output<br />
1 Function is set to “OFF” or “Heating ONLY”.<br />
Units MIN MAX Default<br />
°C 15 27 21.5<br />
°F 59 80.6 70.7<br />
• Proportional: The proportional band used to calculate the proportional component for<br />
Analog Output 1 preheating. Disabled if the Analog Output 1 Function is set to “OFF”<br />
or “Heating ONLY”.<br />
Units MIN MAX Default<br />
°C 0 50 20<br />
°F 0 90 36<br />
• Integral: The integral value used to calculate the integral component for preheating. It<br />
defines the amount of time required for the integral component to add 100% to the<br />
output due to an error of 1 °C. Disabled if the Analog Output 1 Function is set to<br />
“OFF” or “Heating ONLY”.<br />
22<br />
www.prolon.net<br />