In water heating systems the “closed circuit” must be guaranteed, so that the oxygen is not able to be<br />
introduced from external sources. In these conditions carbon steel pipes are not subject to internal corrosion.<br />
Any small amount of oxygen that penetrates when filling, during the heating of the water, is freed and must<br />
be evacuated from the system through the vent valves. Furthermore special additives must be used, which<br />
stop oxygen from causing corrosion.<br />
However, such systems must always be kept filled, even when not operating, or should be emptied and kept<br />
dry, to avoid both air and water being in contact with the metal, a situation that can lead to corrosion. On this<br />
point, after the system has been emptied, it is worth passing forced dry air through the interior, to ensure<br />
complete drying.<br />
Resistance to bimetallic corrosion<br />
Carbon steel components can also be used in mixed installations with non-ferrous metals, such as copper,<br />
aluminum, etc. Importantly, direct contact between carbon steel and stainless steel must be avoided, as this<br />
situation may give rise to bimetallic corrosion. This risk can be reduced by inserting a non-ferrous joint<br />
between the two metals or it can be completely eliminated by using non-ferrous spacers at least 50 mm in<br />
length.<br />
It is absolutely forbidden to create systems with joints in stainless steel and carbon steel pipes, or vice versa.<br />
Resistance to external corrosion<br />
Carbon steel components present an external galvanised or hot zinc plated coating which, however, does<br />
not guarantee on its own a long lasting and effective protection from corrosion. Protection from corrosive<br />
agents must be obtained through insulation, painting or plastic coating on the pipes. In the absence of<br />
protection, a prolonged exposure to moisture, particularly for chased installations, may cause internal<br />
corrosion. It is therefore necessary to cover the pipes with a closed-cell coating or with anti-corrosion tape,<br />
making sure that no part remains uncovered or detachment areas form between the insulating material and<br />
the pipe, where condensation may generate. Felt sheathing must not be used as it holds moisture and<br />
encourages corrosion.<br />
10.4. Carbon steel installations for sprinkler fire fighting and other applications<br />
Carbon steel does not require additional anticorrosion protection in any of the other applications foreseen for<br />
its use.<br />
Note. Please bear in mind that <strong>Eurotubi</strong> advises against using carbon steel for cooling system due to the<br />
considerable risks of corrosion induced by condensation on the cold pipes.<br />
11. SYSTEM COMMISSIONING<br />
11.1 Testing<br />
After installation and before covering, insulation or painting, the system must undergo testing to ensure its<br />
suitable carrying capacity and seal integrity. The test method and result must be necessarily documented in<br />
a report (see annexes 1-4 of this guide).