Pressure test in temperature<br />

(to be carried out immediately afterwards)<br />

Max operating temperature = _____ °C (must be = 11 bar)<br />

Test Pressure = _____ bar (Operating pressure x 1,3)<br />

Duration of the test = _____ minutes (must be ≥ 30 minutes)<br />

The ducts are watertight (∆p = 0)<br />

Place - Date<br />

Signature of the customer or representative:<br />

Signature of the performer or representative:<br />

ANNEX 4<br />

TEST REPORT WITH AIR OR INERT GAS FOR GAS SYSTEMS<br />

SYSTEM:<br />

CUSTOMER:<br />

FIRST PERFORMER:<br />

SECOND PERFORMER:<br />

Following the test it is hereby declared that:<br />

The entire system was visually checked to make sure that all the connections have been made in<br />

accordance with the best working standards<br />

• Test fluid used: air nitrogen<br />

• Volume dell’impianto = _____ liters<br />

• Operating pressure = _____ bar<br />

<strong>System</strong> with operating pressure up to 100 mbar<br />

Load test<br />

Test pressure = _____ bar (must be = 1 bar)<br />

Stabilization time = _____ minutes<br />

Duration of the test = _____ minutes<br />

The ducts are watertight (∆p = 0)<br />

The system has been connected to the network gas<br />

Seal test<br />

Test pressure = _____ bar (must be = 150 mbar)<br />

Stabilization time = _____ minutes<br />

Duration of the test = _____ minutes<br />

The ducts are watertight (∆p = 0)<br />

The system has been connected to the network gas<br />

<strong>System</strong> with operating pressure > 100 mbar and < 1 bar<br />

Combinated load and seal test<br />

Test pressure = _____ bar (must be = 3 bar)<br />

Stabilization time = _____ minutes (must be = 180 minutes)<br />

Duration of the test = _____ minutes (must be = 120 minutes)<br />

The ducts are watertight (∆p = 0)<br />

Place - Date<br />

Signature of the customer or representative:<br />

Signature of the first performer or representative:<br />

Signature of the second performer or representative: