ANNEX 2<br />

TEST REPORT WITH AIR OR INERT GAS FOR DRINKING WATER AND<br />

HEATING SYSTEMS<br />

SYSTEM:<br />

CUSTOMER:<br />

FIRST PERFORMER:<br />

SECOND PERFORMER:<br />

Following the test it is hereby declared that:<br />

The entire system was visually checked to make sure that all the connections have been made in<br />

accordance with the best working standards.<br />

The system was tested internally in n. ______ sections (each test section must be ≤ 100 litres / 0.1 m3)<br />

• Test fluid used: air nitrogen<br />

• Fluid temperature = _____ °C<br />

• Room temperature = _____ °C<br />

• Temperature difference ∆T = _____ °C (must be ≤ 10 °C)<br />

Preliminary test<br />

Test Pressure =<br />

_____ bar (must be = 150 mbar)<br />

Duration of the test = _____ minutes (must be ≥ 120 minutes)<br />

The ducts are watertight (∆p = 0)<br />

Main test<br />

Test pressure = _____ bar (must be ≤ 3 bar for DN ≤50 and ≤ 1 bar for DN >50)<br />

Duration of the test = _____ minutes (must be ≥ 30 minutes)<br />

The ducts are watertight (∆p = 0)<br />

Place - Date<br />

Signature of the customer or representative:<br />

Signature of the first performer or representative:<br />

Signature of the second performer or representative:<br />

ANNEX 3<br />

TEST REPORT WITH WATER FOR HEATING SYSTEMS<br />

SYSTEM:<br />

CUSTOMER:<br />

PERFORMER:<br />

Following the test it is hereby declared that:<br />

The entire system was visually checked to make sure that all the connections have been made in<br />

accordance with the best working standards.<br />

The pipework has been completely aired out.<br />

The operating pressure equals 10 bar.<br />

• Water temperature = _____ °C<br />

• Room temperature = _____ °C<br />

• Temperature difference ∆T = _____ °C (must be ≤ 10 °C)<br />

Pressure test at room temperature<br />

Operating pressure = _____ bar<br />

Test Pressure = _____ bar (Operating pressure x 1,3)<br />

Duration of the test = _____ minutes (must be ≥ 30 minutes)<br />

The ducts are watertight (∆p = 0)