16.05.2015 Views

Eurotubi Pressfitting System - Technical Guide ... - Damstahl

Eurotubi Pressfitting System - Technical Guide ... - Damstahl

Eurotubi Pressfitting System - Technical Guide ... - Damstahl

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

For these systems, both the stainless steel and the carbon steel <strong>Eurotubi</strong> <strong>Pressfitting</strong> <strong>System</strong> can be used.<br />

In any case it is worthwhile to remember that the operating temperature and pressure are two fundamental<br />

elements to know when choosing the type of material. The maximum operating pressure is 16 bar.<br />

In carbon steel systems, the presence of moisture may generate corrosion. Installing a dryer is essential.<br />

Finally it is necessary to wet the o-rings with water before assembling the joints.<br />

20. How long can a <strong>Eurotubi</strong> pressfitting system last?<br />

A system made with <strong>Eurotubi</strong> pressfittings, with approved connecting pipes, with the correct pressing tools<br />

and by closely following the instructions in the <strong>Technical</strong> <strong>Guide</strong> is bound to last at least 20 years. However,<br />

this indication does not constitute a legal guarantee.<br />

Our company and our products strictly follow the legal provisions concerning the guarantees provided by the<br />

seller.<br />

ANNEX 1<br />

TEST REPORT WITH WATER FOR DRINKING WATER SYSTEMS<br />

SYSTEM:<br />

CUSTOMER:<br />

PERFORMER:<br />

Following the test it is hereby declared that:<br />

The entire system was visually checked to make sure that all the connections have been made in<br />

accordance with the best working standards.<br />

The filling water is filtered and does not contain particles ≥ 150 µm.<br />

The pipework has been completely aired out.<br />

The operating pressure equals 10 bar.<br />

• Water temperature = _____ °C<br />

• Room temperature = _____ °C<br />

• Temperature difference ∆T = _____ °C (must be ≤ 10 °C)<br />

Preliminary test<br />

Test Pressure =<br />

_____ bar (must be ≤ 6 bar)<br />

Duration of the test = _____ minutes (must be ≥ 15 minutes)<br />

The ducts are watertight (∆p = 0)<br />

Main test<br />

Test pressure =<br />

_____ bar (must be = 11 bar)<br />

Duration of the test = _____ minutes (must be ≥ 30 minutes)<br />

The ducts are watertight (∆p = 0)<br />

Place - Date<br />

Signature of the customer or representative<br />

Signature of the performer or representative: