Eurotubi Pressfitting System - Technical Guide ... - Damstahl
Eurotubi Pressfitting System - Technical Guide ... - Damstahl
Eurotubi Pressfitting System - Technical Guide ... - Damstahl
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
For these systems, both the stainless steel and the carbon steel <strong>Eurotubi</strong> <strong>Pressfitting</strong> <strong>System</strong> can be used.<br />
In any case it is worthwhile to remember that the operating temperature and pressure are two fundamental<br />
elements to know when choosing the type of material. The maximum operating pressure is 16 bar.<br />
In carbon steel systems, the presence of moisture may generate corrosion. Installing a dryer is essential.<br />
Finally it is necessary to wet the o-rings with water before assembling the joints.<br />
20. How long can a <strong>Eurotubi</strong> pressfitting system last?<br />
A system made with <strong>Eurotubi</strong> pressfittings, with approved connecting pipes, with the correct pressing tools<br />
and by closely following the instructions in the <strong>Technical</strong> <strong>Guide</strong> is bound to last at least 20 years. However,<br />
this indication does not constitute a legal guarantee.<br />
Our company and our products strictly follow the legal provisions concerning the guarantees provided by the<br />
seller.<br />
ANNEX 1<br />
TEST REPORT WITH WATER FOR DRINKING WATER SYSTEMS<br />
SYSTEM:<br />
CUSTOMER:<br />
PERFORMER:<br />
Following the test it is hereby declared that:<br />
The entire system was visually checked to make sure that all the connections have been made in<br />
accordance with the best working standards.<br />
The filling water is filtered and does not contain particles ≥ 150 µm.<br />
The pipework has been completely aired out.<br />
The operating pressure equals 10 bar.<br />
• Water temperature = _____ °C<br />
• Room temperature = _____ °C<br />
• Temperature difference ∆T = _____ °C (must be ≤ 10 °C)<br />
Preliminary test<br />
Test Pressure =<br />
_____ bar (must be ≤ 6 bar)<br />
Duration of the test = _____ minutes (must be ≥ 15 minutes)<br />
The ducts are watertight (∆p = 0)<br />
Main test<br />
Test pressure =<br />
_____ bar (must be = 11 bar)<br />
Duration of the test = _____ minutes (must be ≥ 30 minutes)<br />
The ducts are watertight (∆p = 0)<br />
Place - Date<br />
Signature of the customer or representative<br />
Signature of the performer or representative: