Overview of Alarms 11/2006<br />

NCK alarms<br />

4077 New value %1 of MD %2 not set. Requested %3 bytes too much %4<br />

memory.<br />

Parameters: %1 = New value of machine data<br />

%2 = Machine data number<br />

%3 = Number of bytes requested that exceeded availability<br />

%4 = Type of memory<br />

Definitions: An attempt was made to enter a new value in the specified memory configuration machine data. It was<br />

not possible to modify the value, as this would have cleared the contents of the user memory. This<br />

was because the memory requested exceeded the available capacity.<br />

The third parameter specifies the number of bytes by which the maximum user memory was<br />

exceeded.<br />

The fourth parameter specifies the type of memory whose limit was exceeded.<br />

- "D" stands for dynamic or non-buffered user memory (this is where, for example, the LUD variables<br />

are stored and the interpolation buffer size is entered). The capacity of this memory type is defined by<br />

the current memory configuration and the value in MD MM_USER_MEM_DYNAMIC (18210).<br />

- "S" stands for static or buffered user memory (this is where part programs, offset data, R parameters,<br />

tool data, etc. are stored). This memory type is defined by the current memory configuration and the<br />

value in MD MM_USER_MEM_BUFFERED (18230).<br />

- "iS" stands for internal static or buffered user memory. This memory type is defined by the current<br />

memory configuration (not settable). A few NCK functions use this memory.<br />

Reaction: Alarm display.<br />

Remedy: If the modification was unintentional, ignore the error message and continue. The alarm has no<br />

negative effects. The remedy depends on the access rights and the current memory configuration of<br />

the NCK.<br />

- The intended change is not possible -> try again with a smaller value. Observe the change in the<br />

number of bytes.<br />

- Buy more memory? This option depends on the model in use. (Not possible if parameter 4 equals<br />

"iS").<br />

- The NCK user memory may have been set smaller than it could be. The machine data (see above)<br />

can be changed with appropriate access rights.<br />

- If parameter 4 equals "iS" and no synchronous actions are used, then<br />

$MN_MM_ACTFILESYS_LOG_FILE_MEM[2] = 0 can be set. Otherwise the desired machine data<br />

change cannot be made.<br />

Program Clear alarm with the Delete key or NC START.<br />

Continuation:<br />