Rosemount Tank Radar REX<strong>Reference</strong> <strong>Manual</strong>308018EN, Edition 3BSeptember 2007NOTE!Tank Address corresponds to Pos. in the <strong>FCU</strong> Properties window inWinSetup, see page 2-4. It is important to keep in mind that in WinSetup Pos.starts at 1, but in the Configuration Tools software, Tank Address starts at 0.That is, if a gauge has Tank Address 2 it corresponds to Pos. 3 in TankMaster.Gauge Type is the type of gauge being configured. Only gauges available inthe drop-down list can be used. The following gauge types are available:• GPE ® 31422• GPE ® 31422 Rex• GPE ® 31423• GPE ® 31423 Metric<strong>FCU</strong> Port is the physical port of the <strong>FCU</strong> that is used to communicate with thegauge.Gauge Address is the physical (fieldbus) address of the gauge.Units allow the configuration of level, temperature, density, pressure, volumeand mass units which the gauge returns. Recommended setting is AUTO.Flow Rate Damping and Integration provide a way of filtering out leveldeviation to provide more consistent flow rate readings. They should be left asthe default values unless advised otherwise by competent personnel.2-30 Section 2. Configuration