Q PI Gain [O43]Q PI controller P gain.Default: 0.10Range 0.00 - 1.00Q PI Time [O44]Q PI controller I time.Default: 0.1sRange 0.0 - 10.0sQ Filter time [O45]Q filter time in dynamic/static feedback loop.Default:1sRange 0.0 - 10.0s9.9.5 Frequency controllerparameters [O50]Frequency type [O51]Use frequency observer to handle variations in supplyfrequency.Default:ObserverObserver 0 Use observerO43 Q PI GainStp 0.10O44 Q PI TimeStp 0.1sO45 Q FilterStpFixed 1 Use fixed frequency1sO51 Freq TypeStp Observer9.9.6 View energy status [O80]Energy from Supply [O81]Energy from Supply (Total = Motoring - Generating).Unit:Resolution:Energy to Motor [O82]Energy delivered to Motor (Motoring mode).Unit:Resolution:Wh1WhEnergy to Supply [O83]Energy delivered to Supply (Generating mode).Unit:Resolution:Wh1WhWhReset energy [O84]Clear all energy Wh counters [O81] - [O83]Default:No 0O81 Energy SupplStp1WhO82 Energy MotorStp1WhO83 Energy GenStp1Wh1WhO84 Reset EnergyStpNoNoYes 1 Clear Wh counters.42 Functional Description for AFR unit <strong>Emotron</strong> AB 01-5076-01r1