Kingfisher PLUS+
Kingfisher G30 Manual - ioSelect
Kingfisher G30 Manual - ioSelect
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
MX4 Digital Outputs<br />
Outputs per card 16<br />
Rated Switched Voltage 12 to 24 VDC<br />
Output Type<br />
Transistor, Open Collector, Current Sinking<br />
Output Grouping 2 groups: outputs 1 to 4 and outputs 5 to 8<br />
Each group has a separate common<br />
Maximum Switched<br />
60 VDC<br />
Voltage<br />
Maximum Switched<br />
Current<br />
Isolation<br />
Output Protection<br />
Output Update Time<br />
Failsafe<br />
Pulse / Frequency<br />
Generation<br />
100 mA per channel, self limited<br />
500 V RMS channel to logic<br />
100 V RMS channel to channel between input groups<br />
250 V RMS channel to field power<br />
250 V RMS channel to Earth<br />
250 V RMS channel to other types of IO channels (DI, AI and AO)<br />
No isolation between channels in the same group<br />
Yes. Protected against reverse polarity and transient over voltage and current<br />
1 ms (for all channels)<br />
Yes. Software configurable on any channel(s). If failsafe is disabled, output<br />
holds last state. Failsafe is triggered after 10 seconds of no communications to<br />
the G30.<br />
High Speed:<br />
10 kHz maximum, 1 Hz minimum @ 50% nominal duty cycle<br />
Configurable on channels 1 to 4<br />
Accurate to 0.01%<br />
Low Speed:<br />
500 Hz maximum @ 50% nominal duty cycle<br />
Configurable on channels 5 to 16<br />
Accurate to 2% @ 500 Hz, 0.5% @ 100 Hz, 0.1% @ 1 Hz<br />
Configurable Pulse ON or OFF time: 1 to 16,000 ms<br />
Note: Low Speed pulse frequencies are determined by the time it takes to generate one<br />
pulse ie. Pulse Period = Pulse ON + Pulse OFF times. Pulse frequency (Hz) = 1000 /<br />
Pulse Period (ms).<br />
G30 Hardware Manual 1.3 www.rtunet.com/support Page 24