Kingfisher PLUS+
Kingfisher G30 Manual - ioSelect
Kingfisher G30 Manual - ioSelect
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
2. Comms Cards<br />
Isolated Serial Card (OPT-SER)<br />
FEATURES<br />
2.5 kV Isolation<br />
RS232 / RS422 / RS485 Interface<br />
Port Pinout<br />
RJ45 Pin RS232 RS422 /<br />
RS485*<br />
1 DSR NC<br />
2 DCD NC<br />
3 DTR NC<br />
4 GND GND<br />
5 RXD RX-<br />
6 TXD TX-<br />
7 CTS RX+<br />
8 RTS TX+<br />
RJ45 Socket<br />
87654321<br />
(EIA-561 / RS232D Standard)<br />
RJ45 Plug<br />
12345678<br />
Note: the above pin numbering is<br />
opposite to CP-11/21/30, PC-1 and LP-1<br />
ports.<br />
* Connect TX- and RX- together to obtain LINE- (RS485) and connect TX+ and RX+ together to obtain LINE+ (RS485).<br />
The Isolated serial card supports full hardware flow control.<br />
Isolated Serial Card Specifications<br />
Baudrate<br />
300 to 115200 bps<br />
Data Format 8 data bits, no parity, 1 stop (8, N, 1)<br />
Interface Types<br />
RS232 or RS422 or RS485<br />
Power Consumption<br />
0.5 W maximum<br />
Environment<br />
Operating Temperature -40 to 70 C<br />
RS422 Line drive<br />
RS485 Line drive<br />
Isolation<br />
Operating Humidity<br />
10 Receivers<br />
32 Receivers<br />
2.5 kV<br />
5-95% RH @ 0 to 40 C non-condensing<br />
G30 Hardware Manual 1.3 www.rtunet.com/support Page 8