certified Qualitysystem<br />

ISO 9001 / EN 29001<br />

Reg. Nr. 10529 A Honeywell Company TTO 872 / 876<br />

Oil burner safety control<br />

For <strong>burners</strong> on hot-air heaters, as well as<br />

<strong>burners</strong> above 30 kg/h in intermittent<br />

operation, 1- or 2-stage.<br />

Flame detectors:<br />

- Photoresistor MZ 770 S<br />

- Flicker detector IRD 911 / 1010<br />

INTRDUCTION<br />

The <strong>oil</strong> burner automatic safety control TTO 872, resp.,<br />

TTO 876 controls and monitors <strong>burners</strong> on hot air heaters,<br />

as well as <strong>burners</strong> with an <strong>oil</strong> consumption of over 30 kg/h<br />

(approved and certifcated acc. to DIN 4787).<br />

If the infrared flicker detector IRD 911 or 1010 is utilized as<br />

flame monitor, even red hot combustion chamber walls<br />

cannot affect the safe operation, since this sensor exclusively<br />

responds to the flame.<br />

The <strong>oil</strong> burner automatic safety control TTO 876 is fully<br />

interchangeable with the type TTO 836. The automatic<br />

control TTO 872 is – with the exception of the flame detector<br />

– compatible with type TTO 810. When replacing type<br />

TTO 810, the photo-cell FZ 711 has also got to be replaced<br />

by an MZ 770 S.<br />

The different heights are compensated <strong>for</strong> by mounting the<br />

pushbutton extension (art. No. 70601).<br />

Instead of the pushbutton extension, it is also possible to<br />

mount the remote reset device FR 870 (art. No. 70700, refer<br />

to the documentation "Remote Reset device FR 870").<br />

The <strong>oil</strong> burner control <strong>boxes</strong> TTO 872.2 / 876.2 are<br />

equipped with a low-voltage protection according to<br />

DIN-EN 230.<br />

TYPES AVAILABLE<br />

TTO 872.2 without connecting terminal <strong>for</strong> <strong>oil</strong> pre-heater<br />

TTO 876.2 with bridging contact and connection <strong>for</strong> <strong>oil</strong><br />

pre-heater.<br />

CONSTRUCTIONAL FEATURES<br />

The automatic control is housed in a non-inflammable,<br />

transparent, plug-in type plastic case and contains the<br />

thermo-mechanical and electronic combined time element,<br />

the flame monitor part and the reset device.<br />

On the top of the unit there are the illuminated pushbutton<br />

<strong>for</strong> indication of malfunctions and reset, as well as the screw<br />

<strong>for</strong> central mounting.<br />

The base can be equipped with additional loop terminals<br />

and - together with the various possibilities <strong>for</strong> cable entry<br />

- enables a universal wiring.<br />

1<br />

TECHNICAL DATA<br />

400e/05/94<br />

Operating voltage 220 / 240 V (-15... +10%)<br />

50 Hz (40 - 60 Hz)<br />

Rating fuse max. 10 A rapid, 6 A slow<br />

Power consumption approx. 5 VA<br />

Max. load per output 4 A ohmic (resistive)<br />

valve outputs 2 A ohmic (resistive)<br />

total 6 A ohmic (resistive)<br />

Pre-purge time 20 sec<br />

Pre-ignition time 20 sec<br />

Post-ignition time 2 - 4 sec<br />

Delay time valve 2 approx. 40 sec<br />

Ignition safety time<br />

Waiting period after shut-<br />

5 sec max.<br />

down due to malfunction<br />

Flame detector<br />

approx. 60 sec<br />

MZ 770 S <strong>for</strong> side-on and end-on viewing<br />

IRD 911 / 1010 <strong>for</strong> side-on and end-on viewing<br />

Light sensitivity MZ 770 S<br />

Detector current during<br />

better than 8 Lux<br />

operation<br />

Connection to<br />

flame detector<br />

min. 48 μA<br />

MZ 770 S 2 m cable length maximum<br />

IRD 911 / 1010 up to 100 m cable length<br />

Weight, incl. base 0.25 kg<br />

Mounting position Any<br />

Insulation Standard IP 44<br />

Recommended ambient<br />

operating temperatur <strong>for</strong><br />

control and flame detector -20° C... +60° C