SATRONIC - Control boxes for oil burners

SATRONIC - Control boxes for oil burners

SATRONIC - Control boxes for oil burners

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

certified Qualitysystem<br />

ISO 9001 / EN 29001<br />

Reg. Nr. 10529<br />

Ammeter<br />

For measuring the current from the probe or<br />

photo diode in gas and <strong>oil</strong> <strong>burners</strong> with<br />

ionisation, UV or photo-cell flame detection.<br />

INTRODUCTION<br />

The Ionimeter is particularly suitable <strong>for</strong> measuring the<br />

current from the probe or photo diode in gas and <strong>oil</strong> <strong>burners</strong><br />

with ionisation, UV or photo-cell flame detection.<br />

When measuring this current, the Ionimeter is connected<br />

between the burner control box and the flame detector, by<br />

way of the + and - terminals.<br />

Care must be taken to observe correct polarity when<br />

measuring the current from UV or ionisation detectors.<br />

These measurements are very easily carried out on Satronic<br />

burner control <strong>boxes</strong>, especially when the appropriate test<br />

baseplate is fitted.<br />

The test baseplate is equipped with two plug sockets <strong>for</strong><br />

connecting the leads, and a jumper switch <strong>for</strong> bridging the<br />

Ionimeter.<br />

TECHNICAL DATA<br />

Sensitivity ranges 10 mA<br />

1 mA<br />

100 mA<br />

10 mA<br />

Voltage max. 250 V<br />

Overload fuse rating 20 mA<br />

Only high-impedance power sources should be used <strong>for</strong><br />

calibration purposes (Ri 500 kW).<br />

ACCESSORIES<br />

Leather case<br />

2 test leads with banana-type plugs<br />

2 test clips<br />

A Honeywell Company<br />

1<br />

Ionimeter<br />

CONNECTING THE EARTH TERMINAL<br />

780e/10/92<br />

Additionally, the earth/gound terminal can be connected to<br />

the burner earth (earth terminal on baseplate). By operating<br />

the rocker switch between the minus and earth terminals, in<br />

switch position "earth", an artificial detector probe current<br />

flows directly to the burner earth/ground and activates the<br />

flame relay.<br />

Following this procedure, it is very easy to adjust the<br />

ionisation or UV probe to the optimal setting. Flame signal<br />

strength can be monitored continuously on the Ionimeter,<br />

and burner shutdown, caused by an interruption or a drop<br />

in the current from the detector, is not possible.<br />

CAUTION<br />

In this switch position, the valves remain open after the loss<br />

of the flame.