certified Qualitysystem<br />

ISO 9001 / EN 29001<br />

Reg. Nr. 10529 A Honeywell Company US 7910<br />

Adaptor Baseplate<br />

Adaptor baseplate <strong>for</strong> the MMI 810<br />

model 32 / 33 or TTI 790 model 33<br />

gas burner control <strong>boxes</strong> <strong>for</strong> replacement of<br />

the GBR 681 control box.<br />

INTRODUCTION<br />

The US 7910 adaptor baseplate together with an MMI 810<br />

model 32 / 33 or TTI 790 model 33 can be used to replace<br />

an old GBR 681 unit.<br />

It is not necessary to rewire the burner system. In two-stage<br />

<strong>burners</strong>, valve 2 can be connected to terminal A on the<br />

adaptor baseplate.<br />

The MMI 810 control box then gives the release signal to<br />

the burner second stage approx. 12 sec. after flame establishment.<br />

Terminals<br />

MMI 810 /<br />

TTI 790<br />

US 7910<br />

Baseplate<br />

terminals<br />

GBR 681<br />

Mp<br />

Ph<br />

max. 10A<br />

1 2 3 4 5<br />

HS<br />

GW<br />

V1<br />

1<br />

Insert as per DIN 4788<br />

1 2 3 4 5 6 7 8 9<br />

IS<br />

RT<br />

ST<br />

MMI 810 model 33<br />

- 1st stage rating max. 120 KW / 80.000 kcal/h<br />

MMI 810 model 32<br />

- 1st stage rating max. 350 KW / 300.000 kcal/h<br />

TTI 790 model 33<br />

- start rating max. 120 KW / 80.000 kcal/h<br />

LW M<br />

625e/10/93<br />

HS Main switch HR Secondary relay V1 Solenoid valve 1st stage<br />

GW Gas proving switch IS Ionisation probe V2 Solenoid valve 2nd stage<br />

ST Safety thermostat Z Ignition LW Air proving switch<br />

RT Regulating thermostat M Burner motor SA Remote lockout indicator<br />

Z<br />

6<br />

SA<br />

HR<br />

7 8<br />

B<br />

A B<br />

V2