12.12.2012 Views

T-Series Climate Changer ® Air Handlers Sizes 3 through ... - Trane

T-Series Climate Changer ® Air Handlers Sizes 3 through ... - Trane

T-Series Climate Changer ® Air Handlers Sizes 3 through ... - Trane

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Barometric Relief Economizer<br />

Figure A-5 depicts a typical T-<strong>Series</strong><br />

<strong>Climate</strong> <strong>Changer</strong> <strong>®</strong> air handler with a<br />

barometric relief economizer.<br />

Barometric relief offers some positive<br />

space pressure control. The equipment<br />

consists of an economizer section with<br />

a damper in the return air path that<br />

opens upon an increase in pressure<br />

difference between the space and the<br />

outside.<br />

The supply fan must over-pressurize<br />

the space to allow for proper operation<br />

of the barometric damper. It should<br />

only be used in systems that have<br />

extremely low return air static<br />

requirements. In other systems, it is<br />

recommended that a powered system<br />

such as return fan or exhaust fan<br />

economizer be used instead of<br />

barometric relief.<br />

Application Considerations:<br />

• Size the supply fan to handle<br />

100 percent outside air operation (i.e.<br />

OA hood, OA dampers, filters, coil(s)<br />

and other accessories, plus supply air<br />

ductwork).<br />

• Set up system for maximum delivery at<br />

100 OA economizer mode. Turn on all<br />

remote exhaust fans. Measure the<br />

space static pressure, and adjust<br />

barometric relief damper to produce a<br />

slight positive space pressure.<br />

• Only when the unit is at or near<br />

100 percent OA (return air damper is<br />

closed) will the exhaust section become<br />

sufficiently pressurized to open the<br />

barometric damper.<br />

Meeting ASHRAE<br />

Requirements<br />

ASHRAE Standard 62-89 sets minimum<br />

ventilation rates and defines acceptable<br />

indoor air quality (IAQ) to “avoid<br />

adverse health effects.” It also presents<br />

general system and equipment<br />

requirements for outdoor airflow, air<br />

distribution, design documentation and<br />

microbial growth control. In short,<br />

Standard 62 dramatically impacts the<br />

design, layout and arrangement of the<br />

air handler and its components.<br />

Applications<br />

Providing Adequate<br />

Ventilation <strong>Air</strong>flow<br />

ASHRAE Standard 62-1989 specifies a<br />

per-person outdoor air requirement of<br />

15 to 20 cfm in commercial office<br />

spaces. (Other types of occupied spaces<br />

such as operating rooms require even<br />

higher ventilation rates.) It also<br />

mandates provision for measuring the<br />

amount of outdoor air brought into the<br />

building as proof of compliance.<br />

Consequently, it’s important to include<br />

a means of monitoring airflow in your<br />

T-<strong>Series</strong> <strong>Climate</strong> <strong>Changer</strong> air handler<br />

designs.<br />

Direct measurement of airflow –<br />

i.e., either a factory-mounted Traq damper assembly or a duct mounted<br />

hot-wire-anemometer or pitot-tube<br />

monitoring station provides greater<br />

accuracy and reliability than indirect<br />

monitoring methods such as<br />

mixed-temperature or tracer-gas<br />

calculations, fan-inlet monitors,<br />

fixed-position dampers or<br />

fixed-differential pressure plates.<br />

See “AHU Components: Mixing Box<br />

Section” later in this section for a brief<br />

summary of the Traq damper’s<br />

operating characteristics and<br />

application considerations.<br />

Figure A-5 - Barometric Relief Unit<br />

13<br />

Protecting Hydronic Coils<br />

from Freezing<br />

Bringing more outdoor air into the air<br />

handler to satisfy Standard 62’s<br />

ventilation requirement increases the<br />

likelihood of air stratification. If a layer<br />

of air below freezing moves <strong>through</strong><br />

the air handler, it can damage<br />

unprotected hydronic cooling and<br />

heating coils. Traditionally, a low-limit<br />

thermostat (or “freeze-stat”) installed<br />

on the entering-air side of the cooling<br />

coil trips when it detects a dangerously<br />

low air temperature. That stops the<br />

supply fan, closes the outdoor air<br />

damper and ultimately degrades the<br />

building’s indoor air quality.<br />

It’s important to design the air handler<br />

so that it effectively treats the required<br />

amount of outdoor air regardless of<br />

temperature without risking coil<br />

damage, tripping the low-limit<br />

thermostat or compromising indoor air<br />

quality. Following are several means of<br />

providing coil protection. Choose the<br />

technique that best suits the<br />

application’s requirements.<br />

• Drain the coils. This approach requires<br />

fully drainable coils, vent and drain<br />

connections on every coil, plus shutoff<br />

valves to isolate them from the<br />

chiller(s).<br />

• Add glycol to the cooling system water<br />

to lower its freezing point.<br />

• Preheat the outdoor airstream with a<br />

steam coil, hot-water coil or<br />

energy-recovery device to raise its<br />

temperature above freezing and<br />

eliminate any entrained snow before it<br />

reaches the cooling coil.<br />

• Introduce ventilation air downstream of<br />

the cooling coil with dual-path or<br />

bypass techniques.<br />

• Use an air blender to improve mixing<br />

of the outdoor and recirculated<br />

airstreams.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!