Table 35-1 — Coil Data<br />

1/2" Unit Coils Area (Ft 2 ) Qty-Size<br />

UW,UU,UF 34.10 1-57x86<br />

Shipping Coils<br />

Full 30.14 1-18x85<br />

1-33x85<br />

Modified 21.25 2-18x85<br />

Table 35-2 — Coil Availability<br />

Module Size 1/2" Unit Coils<br />

Shipping<br />

Coils<br />

Small 2 Row 1 Row<br />

Medium<br />

Medium Large<br />

2-8 Row 1-4 Row<br />

Coil<br />

Medium Large<br />

2-8 Row 1-8 Row<br />

Coil w/ Access 2-8 Row 1-4 Row<br />

Table 35-3 — 1/2" Unit Coil Water<br />

Connection - <strong>Sizes</strong> (inches)<br />

UW/UU<br />

Header Height 57<br />

Supply 2 1/2<br />

Return 2 1/2<br />

Drain and Vent 3/8<br />

Shipping coil connections are located on page 71.<br />

See pages 71-80 for refrigerant coil connections and<br />

circuiting.<br />

Unit<br />

<strong>Sizes</strong><br />

All dimensions are in inches.<br />

54<br />

Size 35<br />

Sections Length (inches) Weight (lbs.)<br />

FiIter /Mixing 48 933<br />

Economizer 72 1291<br />

Exhaust 16 265<br />

<strong>Air</strong> Blender 39 822<br />

Flat Filter 11.5 235<br />

Angled Filter 31 545<br />

Bag Filter 48 698<br />

Cartridge Filter 31 494<br />

Small Blank/ Inspection 11.5 130<br />

Medium Blank/ Access 16 169<br />

Medium Large Blank/ Access 31 334<br />

Large Blank/ Access 48 541<br />

Small Coil 11.5 448<br />

Medium Coil 16 897<br />

Medium Large Coil 31 1759<br />

Large Coil 48 1986<br />

Moisture Eliminator 11.5 347<br />

Internal Face I Bypass 16 425<br />

Face Damper 16 425<br />

Front Horizontal Discharge Fan 62 -<br />

FC Fan - 2289<br />

BI / AF Fan - 2389<br />

Plenum Fan - 1426<br />

Q Fan (Q) - 2842<br />

Q Fan (R) - 3018<br />

Bottom Vortical Discharge Fan 73.5 -<br />

FC Fan - 2419<br />

BI / AF Fan - 2518<br />

Plenum Fan - 1555<br />

Diffuser 16 293<br />

Discharge Plenum 48 472<br />

Side Inlet Hood 37.6 124<br />

Back Inlet Hood 31.2 238<br />

Exhaust Hood 37.6 84<br />

Unit End Panels<br />

1. Access module weights include one access door.<br />

6 448<br />

2. Fan module weights include largest ODP motor without IGV.<br />

3. Add mixing module as inlet plenum on horizontal housed or vertical plug return fans.