T-Series Climate Changer ® Air Handlers Sizes 3 through ... - Trane
T-Series Climate Changer ® Air Handlers Sizes 3 through ... - Trane
T-Series Climate Changer ® Air Handlers Sizes 3 through ... - Trane
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
General<br />
Data<br />
Table G-9 — Shipping Coil Water and Steam Connection <strong>Sizes</strong><br />
Coil Type Header Height Supply Return Drain/Vent<br />
W,WA 18,24,30,33 2 1/2 2 1/2 1/2<br />
W 42,48,54 2 1/2 2 1/2 1/2<br />
D,DD,WD,K 18,24,30,33 2 1/2 2 1/2 1/2<br />
P2 18,24,30 3/4 3/4 1/2<br />
P4 18,24,30 1 1 1/2<br />
P8 18,24,30 1 1/4 1 1/4 1/2<br />
WC 18 1 1 1/2<br />
WC 24 1 1/4 1 1/4 1/2<br />
WC 30,33 2 1/2 1 1/2 1/2<br />
NS 18 2 1 1<br />
NS 24 2 1/2 1 1/4 1 1/4<br />
NS 30,33 3 1 1/4 1 1/4<br />
All fittings have female threads.<br />
Table G-10 — 5/8’’ Type F Refrigerant Coil Connections (Inches)<br />
Header No. of 1 Distributor 2 Distributors<br />
Height Circuiting Circuiting Liquid Suction Liquid Suction<br />
Full 12 1 3/8 2 1/8 1 1/8 2 1/8<br />
Half 6 1 1/8 2 1/8 7/8 1 5/8<br />
18 Quarter 3 7/8 1 5/8 N/A N/A<br />
Eighth 2 7/8 1 3/8 5/8 5/8<br />
Sixteenth 1 5/8 5/8 N/A N/A<br />
Full 16 N/A N/A 1 1/8 2 1/8<br />
Half 8 1 1/8 2 1/8 7/8 1 3/8<br />
24 Quarter 4 7/8 1 5/8 7/8 1 3/8<br />
Eighth 2 7/8 1 3/8 5/8 5/8<br />
Full 20 N/A N/A 1 3/8 2 1/8<br />
Half 10 1 3/8 2 1/8 7/8 2 1/8<br />
30 Quarter 5 7/8 2 1/8 N/A N/A<br />
Eighth 4 7/8 1 5/8 7/8 1 3/8<br />
Sixteenth 2 7/8 1 3/8 5/8 5/8<br />
Full 22 N/A N/A 1 3/8 2 1/8<br />
Half 11 1 3/8 2 1/8 Note 1 2 1/8<br />
33 Quarter 7 1 1/8 2 1/8 7/8 1 5/8<br />
Eighth 3 7/8 1 5/8 N/A N/A<br />
Same end connections only.<br />
1. 6-circuit connection is 1 1/8-inches, 5-circuit is 7/8 inches.<br />