General<br />

Data<br />

Table G-9 — Shipping Coil Water and Steam Connection <strong>Sizes</strong><br />

Coil Type Header Height Supply Return Drain/Vent<br />

W,WA 18,24,30,33 2 1/2 2 1/2 1/2<br />

W 42,48,54 2 1/2 2 1/2 1/2<br />

D,DD,WD,K 18,24,30,33 2 1/2 2 1/2 1/2<br />

P2 18,24,30 3/4 3/4 1/2<br />

P4 18,24,30 1 1 1/2<br />

P8 18,24,30 1 1/4 1 1/4 1/2<br />

WC 18 1 1 1/2<br />

WC 24 1 1/4 1 1/4 1/2<br />

WC 30,33 2 1/2 1 1/2 1/2<br />

NS 18 2 1 1<br />

NS 24 2 1/2 1 1/4 1 1/4<br />

NS 30,33 3 1 1/4 1 1/4<br />

All fittings have female threads.<br />

Table G-10 — 5/8’’ Type F Refrigerant Coil Connections (Inches)<br />

Header No. of 1 Distributor 2 Distributors<br />

Height Circuiting Circuiting Liquid Suction Liquid Suction<br />

Full 12 1 3/8 2 1/8 1 1/8 2 1/8<br />

Half 6 1 1/8 2 1/8 7/8 1 5/8<br />

18 Quarter 3 7/8 1 5/8 N/A N/A<br />

Eighth 2 7/8 1 3/8 5/8 5/8<br />

Sixteenth 1 5/8 5/8 N/A N/A<br />

Full 16 N/A N/A 1 1/8 2 1/8<br />

Half 8 1 1/8 2 1/8 7/8 1 3/8<br />

24 Quarter 4 7/8 1 5/8 7/8 1 3/8<br />

Eighth 2 7/8 1 3/8 5/8 5/8<br />

Full 20 N/A N/A 1 3/8 2 1/8<br />

Half 10 1 3/8 2 1/8 7/8 2 1/8<br />

30 Quarter 5 7/8 2 1/8 N/A N/A<br />

Eighth 4 7/8 1 5/8 7/8 1 3/8<br />

Sixteenth 2 7/8 1 3/8 5/8 5/8<br />

Full 22 N/A N/A 1 3/8 2 1/8<br />

Half 11 1 3/8 2 1/8 Note 1 2 1/8<br />

33 Quarter 7 1 1/8 2 1/8 7/8 1 5/8<br />

Eighth 3 7/8 1 5/8 N/A N/A<br />

Same end connections only.<br />

1. 6-circuit connection is 1 1/8-inches, 5-circuit is 7/8 inches.<br />