General<br />
Data<br />
Table G-17 — Type F Coil Circuiting — Modified<br />
Full Half<br />
STANDARD<br />
Quarter Eighth Sixteenth<br />
Unit Header Coil A B C D E<br />
Size Height Rows Dist. Cir/Dist. Dist. Cir/Dist. Dist. Cir/Dist. Dist. Cir/Dist. Dist. Cir/Dist.<br />
3,6 12’’ 2,3,4,6 1 8 1 4 1 2 1 1<br />
8 1 8 1 4 1 2<br />
8,10 18’’ 2,3 1 12 1 6 1 3 1 2 1 1<br />
4 1 12 1 6 1 3 1 2<br />
6,8 1 12 1 6 1 3<br />
12,14 24’’ 2,3,4 2 8 1 8 1 4 1 2<br />
6,8 2 8 1 8 1 4<br />
17 30’’ 2 2 10 1 10 1 5 1 4 1 2<br />
3, 4 2 10 1 10 1 5 1 4<br />
6, 8 2 10 1 10<br />
21 33’’ 2,3 2 11 1 11 1 7 1 3<br />
4,6 2 11 1 11 1 7<br />
8 2 11 1 11<br />
25,30, 2-18’’ 2,3 2 12 2 6 2 3 2 2 2 1<br />
35,40 4 2 12 2 6 2 3 2 2<br />
6,8 2 12 2 6 2 3<br />
50 2-24’’ 2,3,4 4 8 2 8 2 4 2 2<br />
6,8 4 8 2 8 2 4<br />
66 1-24’’ 2,3 2/2 8/11 2 8/11 2 4/7 2 2/3<br />
1-33’’ 4,6 2/2 8/11 2 8/11 2 4/7<br />
8 2/2 8/11 2 8/11<br />
80 2-18’’ 2,3 1/2 12/11 1/2 6/11 1/2 3/7 1/2 2/3<br />
1-33’’ 4,6 1/2 12/11 1/2 6/11 1/2 3/7<br />
8 1/2 12/11 1/2 6/11<br />
100 2,3 4/2 8/10 2/1 8/10 2/1 4/5 2/1 2/4<br />
2-24’’ 4,6 4/2 8/10 2/1 8/10 2/1 4/5<br />
1-30’’ 8 4/2 8/10 2/1 8/10<br />
The notation “2/2” for distributor and “8/11” for circuits per distributor means that 2 distributors feed 8 circuits each and that 2 distributors feed 11 circuits each.<br />