Unit<br />
<strong>Sizes</strong><br />
63<br />
Size 80<br />
Table 80-4 — Unit Pressure Drops (Inches WG)<br />
Damper Face Velocity (FPM)<br />
Ultra Low Leak Dampers Area (ft2 ) 400 500 600 700 800 900 1000 1100 1200<br />
Back or Bottom Damper 40.90 .01 .01 .01 .02 .03 .03 .04 .05 .06<br />
Side Damper (each) 19.26 .01 .01 .02 .02 .03 .04 .05 .05 .06<br />
Protective Grate 44.90 .04 .06 .09 .12 .16 .20 .25 .30 .36<br />
Area (ft 2 ) 600 800 1000 1200 1400 1600 1800 2000 2100<br />
Exhaust or Economizer Return Dampers 19.2 6.02 .03 .05 .06 .09 .11 .14 .18 .19<br />
Internal Face and Bypass* Area (ft 2 ) 400 500 600 700 800 900 1000 1100 1200<br />
Face Area 61.29 .02 .03 .05 .06 .08 .10 .13 .15 .18<br />
Face Damper 79.20 .02 .03 .04 .06 .08 .10 .12 .15 .18<br />
Area (ft 2 ) 1400 1600 1800 2000 2200 2400 2600 2800 3000<br />
Bypass Area 16.91 .43 .56 .71 .87 1.06 1.26 1.48 1.71 1.97<br />
Accessory Face Velocity (FPM)<br />
Accessories Area (ft 2 ) 400 450 500 550 600 650 700 750 800<br />
Moisture-Eliminator 78.75 .01 .01 .02 .03 .03 .03 .04 .04 .05<br />
Diffuser 78.75 .53 .67 .83 1.00 1.19 1.40 1.62 1.86 2.12<br />
Inlet Hood Face Velocity (FPM)<br />
Inlet Hoods Area (ft 2 ) 300 400 500 600 700 800 850 900 950<br />
Inlet Hood w/ Moisture Eliminator .04 .06 .10 .15 .20 .26 .29 .33 .36<br />
Side Inlet Hood 22.65<br />
Back Inlet Hood 48.65<br />
Face Velocity (FPM)<br />
Area (ft 2 ) 1000 1200 1400 1600 1800 2000 2200 2400 2600<br />
<strong>Air</strong> Blenders 28.86 .07 .10 .14 .18 .24 .30 .37 .44 .52<br />
Filter Face Velocity (FPM)<br />
Filters** Area (ft 2 ) 200 250 300 350 400 450 500 550 600<br />
Flat Filters 83.10<br />
2" Throwaway 4-16x25 .27 .29 .30 .32 .34 .37 .39 - -<br />
2" Pleated Media 8-16x20 .52 .54 .55 .57 .59 .62 .64 .70<br />
4" Pleated Media 6-20x25 .52 .53 .54 .56 .57 .59 .61 .64 .66<br />
Permanent 12-20x20 .51 .51 .52 .52 .53 .53 .54 .55 .56<br />
Angled Filters 137.50<br />
2" Throwaway 30-20x25 .27 .29 .30 .32 .34 .37 .39 - -<br />
2" Pleated Media 12-16x25 .52 .54 .56 .57 .59 .62 .64 .67 .70<br />
Permanent .51 .51 .52 .52 .53 .53 .54 .55 .56<br />
Cartridge/Bag Filters* 80.70<br />
6" Cartridge - 65% Eff. 6-20x24 .56 .58 - - - - - - -<br />
6" Cartridge - 85% Eft. 6-20x20 .61 .65 - - - - - - -<br />
6" Cartridge - 95% Eff. 6-24x24 .63 .68 - - - - - - -<br />
12" Cartridge - 65% Eff. 6-24x20 .79 .82 .84 .88 .91 .96 1.00 1.06 1.11<br />
12" Cartridge - 85% Eff. .80 .82 .85 .89 .93 .98 1.03 1.09 1.15<br />
12" Cartridge - 95% Eff. .81 .84 .87 .92 .97 1.03 1.09 1.16 1.24<br />
Bag - 65% Eff. .53 .55 .57 .60 .63 .66 .70 .74 .79<br />
Bag - 85% Eff. .54 .57 .59 .63 .66 .71 .75 .81 .86<br />
Bag - 95% Eff. .55 .59 .62 .67 .72 .78 .84 .91 .99<br />
**Filter pressure drops are based on mid-life data.<br />
Do not exceed maximum filter face velocities shown<br />
Actual pressure drops may be less than shown due to variations in filter brands.<br />
*The bypass in an internal face-and-bypass damper is not sized for 100% airflow. For applications that require 100% bypass, consult your local <strong>Trane</strong> engineer.<br />
*Cartridge/bag filter pressure drops include a 2" throwaway pre-filter pressure drop.<br />
Table 80-5 — Fan Data<br />
A B<br />
Fan Type<br />
C P Q<br />
Design CFM 39375 39375 39375 39375 39375<br />
Size/Type 40 1/4 AF 36 1/2 AF 33 AF 58 1/2 AF 44 1/2 Q-Fan<br />
Max TSP/RPM<br />
Bearing Size<br />
5/996 8/1413 8/1562 6/875 6/1485<br />
Drive Side 2 3/16 2 7/16 2 7/16 2 11/16 1 15/16<br />
Opposite Drive Side 1 7/16 1 7/16 1 7/16 1 7/16 1 15/16<br />
Shaft Size 3 7/16 3 15/16 3 15/16 2 11/16 1 15/16<br />
Outlet Area (Ft2 ) 20.14 16.54 13.51 - 12.33<br />
Motor HP Range<br />
IGV Torque (Inch-Lb.)<br />
15-50 20-75 20-75 7 1/2-60 2-50<br />
2000 FPM (4.0" WC) 100/62 113/27 84/20 262.0 -<br />
3000 FPM (Max. RPM and BHP) 216/140 256/63 189/46 361.0 -<br />
Torques are shown for open/closed operation at 2000 and 3000 fpm fan outlet velocity.<br />
For plug fans torques at shown 4.0" WC and at Max. RPM and BHP.