Table PD-1: Gross <strong>Cooling</strong> Capacities (MBh) 7 1/2 Ton TWA090A Condensing Unit with 7 1/2 Ton TWE090A Air Handler<br />

CFM<br />

Airflow<br />

Enter.<br />

DB<br />

(° F)<br />

Ambient Temperature<br />

85 95 105 115<br />

Entering WB<br />

61 67 73 61 67 73 61 67 73 61 67 73<br />

MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC<br />

2700 75 85 66.9 93.8 56.6 103.2 38.1 81.8 65.3 90.3 55.2 99.3 36.8 78.3 63.5 86.4 53.6 95.2 35.3 74.5 61.7 82.3 52 90.7 33.8<br />

80 85.4 77.9 94.1 64.4 103.2 49.8 82.3 76.4 90.5 62.9 99.4 48.3 78.9 74.7 86.7 61.2 95.2 46.8 75.3 72.8 82.5 59.3 90.8 45.1<br />

85 87.1 87.1 94.2 75.3 103.4 61.2 84.5 84.5 90.7 73.7 99.6 59.7 81.6 81.6 86.8 72 95.4 58.2 78.4 78.4 82.7 70.2 91 56.5<br />

90 91.5 91.5 94.6 86.4 103.6 72.5 88.8 88.8 91.3 84.9 99.6 70.9 85.8 85.8 87.6 83.2 95.5 69.3 82.5 82.5 83.7 81.5 91.1 67.5<br />

3000 75 86.7 69.9 95.5 54.9 104.9 38.8 83.3 68.3 91.9 53.3 100.9 37.5 79.7 66.5 87.9 51.7 96.6 35.9 75.8 64.6 83.6 49.9 92 34.3<br />

80 87.3 82 95.7 67.2 104.9 51.4 84.1 80.4 92 65.5 100.9 49.9 80.6 78.7 88 63.8 96.7 48.3 77 76.9 83.8 61.9 92.1 46.7<br />

85 89.9 89.9 95.9 79 105.1 63.8 87.2 87.2 92.2 77.4 101.1 62.3 84.1 84.1 88.3 75.7 96.9 60.8 80.8 80.8 84.2 73.9 92.4 59.1<br />

90 94.5 94.5 96.6 91.2 105.2 75.9 91.6 91.6 93.1 89.7 101.2 74.3 88.4 88.4 89.4 88.0 97.0 72.7 85.0 85.0 85.1 85.1 92.5 70.9<br />

3300 75 88.1 72.7 96.9 56.6 106.2 39.5 84.6 71.1 93.1 55.1 102.1 38 80.9 69.3 89.1 53.4 97.7 36.4 76.9 67.4 84.7 51.7 93 34.7<br />

80 88.9 85.9 97 69.7 106.3 52.9 85.7 84.3 93.3 68.1 102.2 51.4 81.8 81.8 89.2 66.3 97.9 49.8 78.4 78.4 84.9 64.5 93.2 48.2<br />

85 92.4 92.4 97.3 82.6 106.5 66.3 89.5 89.5 93.6 81 102.4 64.8 86.3 86.3 89.6 79.3 98.1 63.2 82.8 82.8 85.4 77.4 93.3 61.3<br />

90 97.0 97.0 98.4 95.9 106.6 79.2 94.0 94.0 94.9 94.3 102.6 77.6 90.8 90.8 90.8 90.8 98.2 75.9 87.2 87.2 87.3 87.3 93.6 74.2<br />

3600 75 89.2 75.5 98.0 58.3 107.4 40.0 85.8 73.8 94.2 56.7 103.2 38.5 82.0 72.0 90.1 55.1 98.7 36.9 77.9 70.0 85.6 53.3 93.9 35.2<br />

80 90.5 89.7 98.2 72.2 107.5 54.3 86.8 86.8 94.4 70.5 103.3 52.8 83.6 83.6 90.3 68.8 98.9 51.2 80.1 80.1 85.9 66.9 94.2 49.6<br />

85 94.5 94.5 98.5 86.0 107.7 68.6 91.5 91.5 94.8 84.4 103.5 67.2 88.2 88.2 90.8 82.7 99.0 65.3 84.6 84.6 86.5 80.8 94.3 63.5<br />

90 99.3 99.3 99.3 99.3 107.8 82.4 96.2 96.2 96.3 96.3 103.7 80.8 92.8 92.8 92.9 92.9 99.3 79.1 89.2 89.2 89.2 89.2 94.6 77.3<br />

Equal MBH and SHC values constitute dry coil condition. Total Gross <strong>Cooling</strong> Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat<br />

Capacity (SHC) is the total capacity.<br />

All capacities shown are gross and have not considered indoor fan heat.<br />

To obtain net cooling capacities, subtract indoor fan heat.<br />

MBH = Total Gross <strong>Cooling</strong> Capacity<br />

SHC = Sensible Heat Capacity<br />

Table PD-2: Gross <strong>Cooling</strong> Capacities (MBh) 7 1/2 Ton TWA090A Condensing Unit with 10 Ton TWE120A Air Handler<br />

CFM<br />

Airflow<br />

Enter.<br />

DB<br />

(° F)<br />

Ambient Temperature<br />

85 95 105 115<br />

Entering WB<br />

61 67 73 61 67 73 61 67 73 61 67 73<br />

MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC<br />

3100 75 90.8 73.8 99.9 61.9 109.7 40.7 87.4 72.1 96.2 60.4 105.6 39.3 83.4 70.2 92.1 58.8 101.2 37.8 79.2 68.2 87.7 57.1 96.5 36.2<br />

80 91.4 86.7 100.2 70.8 109.7 54 88.1 85.1 96.4 69.3 105.7 52.5 84.4 83.3 92.3 67.4 101.4 50.9 80.3 80.3 87.9 65.5 96.7 49.2<br />

85 94.5 94.5 100.3 83.5 109.9 67.2 91.6 91.6 96.6 81.9 105.9 65.7 88.4 88.4 92.5 80.1 101.6 64.1 84.9 84.9 88.2 78.3 97 62.4<br />

90 99.2 99.2 101 96.5 110.1 80.3 96.2 96.2 97.5 95 106 78.6 92.9 92.9 93.6 93.3 101.7 76.9 89.4 89.4 89.6 89.6 97.1 75.1<br />

3400 75 92.2 76.8 101.4 59.5 111.1 41.3 88.7 75.1 97.6 58 106.9 39.8 84.7 73.2 93.4 56.3 102.4 38.2 80.4 71.2 88.9 54.5 97.6 36.5<br />

80 93.1 90.9 101.6 73.7 111.2 55.6 89.7 89.3 97.7 71.9 107.1 54.1 85.9 85.9 93.5 70.1 102.6 52.5 82.3 82.3 89.1 68.2 97.9 50.8<br />

85 97.0 97.0 101.7 87.3 111.4 69.8 94.0 94.0 98.0 85.7 107.2 68.3 90.7 90.7 93.9 83.9 102.9 66.7 87.1 87.1 89.5 82.0 98.1 65.1<br />

90 101.8 101.8 102.8 101.5 111.4 83.6 98.8 98.8 98.9 98.9 107.3 82.1 95.4 95.4 95.5 95.5 103 80.4 91.8 91.8 91.9 91.9 98.3 78.6<br />

3700 75 93.4 79.8 102.6 61.3 112.2 41.8 89.8 78 98.7 59.7 108 40.3 85.8 76.1 94.4 58 103.4 38.7 81.5 74.1 89.9 56.2 98.5 37<br />

80 94.2 94.2 102.7 76.2 112.4 57.1 91.2 91.2 98.8 74.5 108.2 55.6 87.8 87.8 94.6 72.7 103.7 54 84.2 84.2 90.1 70.8 98.9 52.3<br />

85 99.2 99.2 103 91.0 112.6 72.3 96.1 96.1 99.2 89.4 108.4 70.8 92.7 92.7 95.1 87.6 103.9 69.3 89.0 89.0 90.7 85.7 99.0 67.2<br />

90 104.2 104.2 104.3 104.3 112.7 87.0 101 101 101.1 101.1 108.5 85.4 97.6 97.6 97.6 97.6 104 83.8 93.8 93.8 93.9 93.9 99.3 82.0<br />

4000 75 94.5 82.6 103.6 63 113.2 42.3 90.8 80.8 99.7 61.4 108.9 40.7 86.8 78.9 95.3 59.7 104.2 39.2 82.5 76.9 90.7 57.9 99.3 37.5<br />

80 96.1 96.1 103.8 78.7 113.4 58.5 93.0 93.0 99.8 77.1 109.1 57.0 89.5 89.5 95.5 75.3 104.6 55.5 85.8 85.8 90.9 73.3 99.7 53.8<br />

85 101.2 101.2 104.2 94.5 113.6 74.8 98.0 98.0 100.4 92.9 109.2 73.0 94.5 94.5 96.2 91.1 104.7 71.3 90.7 90.7 91.8 89.3 99.9 69.5<br />

90 106.3 106.3 106.4 106.4 113.7 90.3 103.0 103.0 103.1 103.1 109.4 88.7 99.5 99.5 99.6 99.6 105 87.0 95.6 95.6 95.7 95.7 100.2 85.3<br />

Equal MBH and SHC values constitute dry coil condition. Total Gross <strong>Cooling</strong> Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat<br />

Capacity (SHC) is the total capacity.<br />

All capacities shown are gross and have not considered indoor fan heat.<br />

To obtain net cooling capacities, subtract indoor fan heat.<br />

MBH = Total Gross <strong>Cooling</strong> Capacity<br />

SHC = Sensible Heat Capacity<br />

Performance Data<br />

7 1/2 Tons<br />

14 SS-PRC002-EN