12.12.2012 Views

Split System Cooling Units - Trane

Split System Cooling Units - Trane

Split System Cooling Units - Trane

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Selection<br />

Procedure<br />

<strong>Cooling</strong> Capacity<br />

Step 1 — Calculate the building’s total<br />

and sensible cooling loads at design<br />

conditions. Use the <strong>Trane</strong> calculation<br />

form or any other standard accepted<br />

method.<br />

Step 2 — Size the equipment using<br />

Table PD-1. Match the cooling loads at<br />

design conditions.<br />

Example: The following are the building<br />

cooling requirements:<br />

a. Electrical Characteristics: 460/60/3<br />

b. Summer Design Conditions:<br />

Entering Evaporator Coil:<br />

80° F DB/67° F WB<br />

Outdoor Ambient: 95° F<br />

c. Total <strong>Cooling</strong> Load: 88MBh<br />

d. Sensible <strong>Cooling</strong> Load: 64 MBh<br />

e. Airflow: 3000 cfm<br />

External Static Pressure:<br />

0.77 inches of water gauge<br />

Table PD-1 shows that TWA090A4<br />

with TWE090A has a gross cooling capacity<br />

of 91.1 MBh and 65.9 MBh sensible<br />

capacity at 95° F DB ambient and<br />

3000 cfm with 80° F DB/67° F WB air<br />

entering the evaporator.<br />

To find the net cooling capacities, fan<br />

motor heat must be subtracted. Determine<br />

the total unit static pressure:<br />

External Static: 0.77 in.<br />

Standard Filter: 0.10 in.<br />

Supplementary Electric Heat: 0.23 in.<br />

Total Static Pressure 1.10 in.<br />

Note: The Evaporator Fan Performance<br />

Table has included the effect of<br />

a 1 in. filter already. Therefore, the actual<br />

Total Static Pressure is<br />

1.10 - 0.10 = 1.00 in.<br />

With 3000 cfm and 1.00 inches, Table<br />

PD-19 shows a 1.17 Bhp.<br />

Note: The formula below the table can<br />

be used to calculate Fan Motor Heat:<br />

3.5 X Bhp = MBh<br />

3.5 X 1.17 = 4.09 MBh<br />

Net Total <strong>Cooling</strong> Capacity =<br />

92.0 MBh - 4.10 = 87.90 MBh<br />

Net Sensible <strong>Cooling</strong> Capacity =<br />

65.5 MBh - 4.10 = 61.40 MBh<br />

Heating Capacity<br />

Step 1 — Calculate the building heating<br />

load using the <strong>Trane</strong> calculation<br />

form or any other standard accepted<br />

method.<br />

Step 2 — Size the system heating capacity<br />

to match the calculated building<br />

heating load. The following are building<br />

heating requirements:<br />

a. Total Heating Load: 97.0 MBh<br />

b. 3000 cfm<br />

c. Electric Supplementary Heaters<br />

From Table PD-52, the 34.88 Kw heater<br />

has a capacity of 119,045 Btuh. From<br />

Table ED-5, the 34.88 Kw at 460v indicates<br />

the heater model number is<br />

BAYHTRL435A. This heater will adequately<br />

cover the building’s heating<br />

requirement.<br />

Air Delivery Selection<br />

External static pressure drop through<br />

the air distribution system has been<br />

calculated to be 0.77 inches of water<br />

gauge. From Table PD-51 static pressure<br />

drop through the electric heater is<br />

0.23 inches of water (0.77 + 0.23 = 1.00<br />

in.). Enter Table PD-35 for TWE090A4<br />

at 3000 cfm and 1.00 static pressure.<br />

The standard motor at 821 RPM will<br />

give the desired airflow.<br />

SS-PRC002-EN 9

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!