Performance Data<br />

7 1/2 Tons<br />

Table PD-13: Gross <strong>Cooling</strong> Capacities (MBh) — 7 1/2 Ton TTA090A Condensing Unit Only<br />

Outdoor<br />

Temperature<br />

Suction Temperature Degrees F<br />

In Degrees F<br />

30 35 40 45 50 55<br />

Head press PSIG 166.0 171.0 177.0 182.0 189.0 195.0<br />

65 Cap. Btuh/1000 82.0 90.1 98.6 107.3 116.3 125.4<br />

Unit KW 5.5 5.6 5.7 5.9 6.1 6.3<br />

Head press PSIG 190.0 196.0 202.0 208.0 214.0 221.0<br />

75 Cap. Btuh/1000 78.4 86.1 94.1 102.3 110.8 119.5<br />

Unit KW 6.0 6.1 6.3 6.5 6.7 6.9<br />

Head press PSIG 217.0 223.0 229.0 236.0 242.0 250.0<br />

85 Cap. Btuh/1000 74.4 81.7 89.2 97.1 105.2 113.5<br />

Unit KW 6.6 6.8 6.9 7.1 7.3 7.5<br />

Head press PSIG 247.0 253.0 259.0 266.0 273.0 281.0<br />

95 Cap. Btuh/1000 70.1 77.0 84.2 91.6 99.3 107.3<br />

Unit KW 7.4 7.5 7.7 7.9 8.1 8.3<br />

Head press PSIG 279.0 285.0 292.0 299.0 307.0 315.0<br />

105 Cap. Btuh/1000 65.4 72.0 78.8 85.9 93.3 100.9<br />

Unit KW 8.2 8.4 8.6 8.8 9.0 9.2<br />

Head press PSIG 313.0 320.0 327.0 335.0 343.0 351.0<br />

115 Cap. Btuh/1000 60.50 66.70 73.20 80.00 87.00 94.30<br />

Unit KW 9.17 9.35 9.54 9.73 9.92 10.12<br />

Performance data calculated at 15° F subcooling and 20% superheat and does not include capacity loss<br />

due to refrigerant lines.<br />

Table PD-14: Capacity Curves — 7 1/2 Ton TTA090A Condensing Unit Only<br />

20 SS-PRC002-EN