Performance Data<br />

15 Ton<br />

Table PD-25: Gross <strong>Cooling</strong> Capacities (MBh) — 15 Ton TTA180B Condensing Unit Only<br />

Outdoor<br />

Temperature<br />

Suction Temperature Degrees F<br />

In Degrees F<br />

30 35 40 45 50 55<br />

65 Head pressure PSIG 179.0 186.0 194.0 202.0 210.0 220.0<br />

Capacity BTUH/1000 163.9 179.7 196.2 213.3 231.2 249.9<br />

Unit KW 11.3 11.6 12.0 12.5 12.9 13.4<br />

75 Head pressure PSIG 204.0 211.0 219.0 227.0 236.0 246.0<br />

Capacity BTUH/1000 156.4 171.5 187.2 203.6 220.9 239.0<br />

Unit KW 12.3 12.7 13.1 13.6 14.1 14.6<br />

85 Head pressure PSIG 231.0 239.0 247.0 255.0 265.0 275.0<br />

Capacity BTUH/1000 148.2 162.7 177.7 193.4 210.0 227.4<br />

Unit KW 13.6 14.0 14.5 14.9 15.5 16.0<br />

95 Head pressure PSIG 261.0 269.0 277.0 286.0 296.0 306.0<br />

Capacity BTUH/1000 139.6 153.3 167.6 182.6 198.5 215.2<br />

Unit KW 15.1 15.5 16.0 16.4 17.0 17.5<br />

105 Head pressure PSIG 293.0 301.0 310.0 319.0 329.0 340.0<br />

Capacity BTUH/1000 130.5 143.5 157.1 171.3 186.5 202.5<br />

Unit KW 16.8 17.2 17.6 18.1 18.6 19.2<br />

115 Head pressure PSIG 328.0 336.0 345.0 355.0 365.0 377.0<br />

Capacity BTUH/1000 121.00 133.20 146.10 159.60 174.10 189.30<br />

Unit KW 18.62 19.03 19.47 19.92 20.42 20.94<br />

Performance data calculated at 15° F subcooling and 20% superheat and does not include capacity loss<br />

due to refrigerant lines.<br />

Table PD-26: Capacity Curves — 15 Ton TTA180B Condensing Unit Only<br />

26 SS-PRC002-EN