Performance Data<br />
5 - 20 Ton<br />
Table PD-49: Electric Heat Discharge Plenum and Grille Airflow (CFM)<br />
Tons Unit Model No. Electric Heater<br />
Airflow (CFM)<br />
Model No. Minimum Maximum<br />
5 TWE060A1, B1 BAYHTRL117A 2000 2400<br />
TWE060A3, B3 BAYHTRL315A 2000 2400<br />
TWE060A4, B4 BAYHTRL415A 2000 2400<br />
7 1/2 TWE090A1, B1 BAYHTRL117A 3000 3600<br />
BAYHTRL123A 3375 3600<br />
TWE090A3, B3 BAYHTRL315A 2625 3600<br />
BAYHTRL325A 3000 3600<br />
TWE090A3, B3 BAYHTRL415A 2625 3600<br />
BAYHTRL425A 2625 3600<br />
10 TWE120A1, B1 BAYHTRL117A 3500 4800<br />
BAYHTRL123A 4000 4800<br />
TWE120A3, B3 BAYHTRL315A 4000 4800<br />
BAYHTRL325A 3500 4800<br />
TWE120A3, B3<br />
Notes:<br />
1 When wired for 460 Volt.<br />
1<br />
BAYHTRL415A 3500 4800<br />
BAYHTRL425A 3500 4800<br />
15 TWE180B3 BAYHTRM330A 5250 7200<br />
TWE180B4 BAYHTRM430A 5250 7200<br />
20 TWE240B3 BAYHTRM330A 7000 9600<br />
TWE240B4 BAYHTRM430A 7000 9600<br />
Table PD-50: Discharge Plenum and Grille Assembly Throw Distance (ft) — Air Handler<br />
Unit Tons Model No. CFM Louver Angle Deflection Position<br />
Straight 20º 40º 55º<br />
5 TWE060A 1600 42 31 26 20<br />
TWE060B 1800 46 37 29 22<br />
2000 48 43 33 24<br />
2200 51 50 36 25<br />
2400 54 57 39 29<br />
TWE090A 2400 52 43 35 29<br />
TWE090B 2700 55 48 38 31<br />
3000 58 53 42 32<br />
3300 62 57 46 35<br />
3600 66 60 50 37<br />
TWE120A 3200 56 46 38 30<br />
TWE120B 3600 62 51 42 33<br />
4000 66 57 47 35<br />
4400 71 62 52 38<br />
4800 76 67 56 42<br />
15 TWE180B 4900 47 38 32 25<br />
5400 52 44 37 29<br />
6000 57 49 41 32<br />
6600 61 53 43 34<br />
7200 65 57 46 35<br />
20 TWE240B 6400 56 46 38 30<br />
7200 62 51 42 33<br />
8000 66 57 47 35<br />
8800 71 62 52 38<br />
9600 76 67 56 42<br />
Throw distance values are based on a terminal velocity of 75 FPM.<br />
Throw distance values at other terminal velocities may be established by multiplying throw distances in<br />
the table above by throw factor:<br />
Terminal Velocity Throw Factor<br />
50 FPM x 1.50<br />
100 FPM x .75<br />
150 FPM x .50<br />
SS-PRC002-EN 37