Performance Data<br />

10 Ton<br />

Table PD-15: Gross <strong>Cooling</strong> Capacities (MBh) — 10 Ton TTA120A Condensing Unit Only<br />

Outdoor<br />

Temperature<br />

Suction Temperature Degrees F<br />

In Degrees F<br />

30 35 40 45 50 55<br />

Head press PSIG 172.0 178.0 185.0 192.0 201.0 209.0<br />

65 Cap. Btuh/1000 112.5 123.7 135.5 147.9 160.9 174.6<br />

Unit KW 8.0 8.2 8.4 8.7 8.9 9.2<br />

Head press PSIG 196.0 203.0 210.0 218.0 226.0 235.0<br />

75 Cap. Btuh/1000 107.5 118.2 129.4 141.3 153.9 167.0<br />

Unit KW 8.7 8.9 9.1 9.4 9.7 10.0<br />

Head press PSIG 223.0 230.0 237.0 245.0 254.0 263.0<br />

85 Cap. Btuh/1000 102.2 112.3 123.1 134.6 146.6 159.2<br />

Unit KW 9.5 9.7 10.0 10.3 10.6 10.9<br />

Head press PSIG 252.0 260.0 267.0 276.0 285.0 294.0<br />

95 Cap. Btuh/1000 96.5 106.3 116.6 127.5 139.1 151.2<br />

Unit KW 10.4 10.7 11.0 11.3 11.6 11.9<br />

Head press PSIG 285.0 292.0 300.0 309.0 318.0 328.0<br />

105 Cap. Btuh/1000 90.6 99.9 109.8 120.3 131.4 142.9<br />

Unit KW 11.5 11.8 12.0 12.4 12.7 13.0<br />

Head press PSIG 319.0 327.0 336.0 345.0 355.0 365.0<br />

115 Cap. Btuh/1000 84.50 93.40 102.90 112.90 123.40 134.40<br />

Unit KW 12.64 12.94 13.25 13.58 13.91 14.26<br />

Performance data calculated at 15° F subcooling and 20% superheat and does not include capacity loss<br />

due to refrigerant lines.<br />

Table PD-16: Capacity Curves — 10 Ton TTA120A Condensing Unit Only<br />