Technical Details – Components for Fluorescent Lamps<br />

Starters for fluorescent lamps<br />

As mentioned above, the operation of fluorescent lamps also requires starters in addition to ballasts. A<br />

distinction is made between glow starters, which are also available with automatic cut-outs, and electronic<br />

starters. The correct choice of voltage and power range is crucial. Starters are available for 220–240 V<br />

and for 110–127 V mains voltage. The latter are also required for twin-lamp operation (e.g. 2x18 W at<br />

230 V).<br />

Operating SL-series <strong>VS</strong> ballasts (100–127 V) depends on the use of a 220–240 V starter as these operating<br />

devices are high-reactance transformers that supply higher voltages to the lamp. Starters should only<br />

be used with starter contacts with a hardness value of at least HB 100.<br />

Assembly Instructions for<br />

Electromagnetic Ballasts<br />

For mounting and installing of electromagnetic ballasts for fluorescent lamps<br />

Mandatory regulations<br />

DIN VDE 0100 Erection of low voltage installations<br />

EN 60598-1<br />

Luminaires – part 1: general requirements and tests<br />

EN 61347-1<br />

Operating devices for lamps – part 1: general and safety requirements<br />

EN 61347-2-8<br />

Operating devices for lamps – part 2-8: special requirements for ballasts<br />

for fluorescent lamps<br />

EN 60921<br />

Ballasts for fluorescent tube lamps – performance requirements<br />

EN 50294<br />

Methods for measuring the total input power of ballast-lamp circuits<br />

EN 55015<br />

Maximum values and methods of measurement for RFI suppression<br />

in electrical lighting installations and similar electrical appliances<br />

EN 61000-3-2 Electromagnetic Compatibility (EMC) – part 3:<br />

maximum values – main section part 2: maximum values for mains harmonics<br />

(device input current up to and including 16 A per conductor)<br />

EN 61547 Installations for general lighting purposes – EMC immunity requirements<br />

Technical specifications<br />

Operating voltage range<br />

<strong>VS</strong> ballasts can be operated at the specified mains voltage within a tolerance range<br />

of ±10%<br />

Leak current<br />

≤ 0.1 mA per ballast<br />

Error current Impulse-resistant leak-current protection must be installed. Distribute the luminaires to<br />

phases L1, L2 and L3; install tri-phase FI switches. If permissible, install FI switches with<br />

30 mA leak current; connect no more than 15 luminaires as FI switches can be triggered<br />

at half the leak current value.<br />

Power factor Inductive ballasts: λ 0.5<br />

Parallel-compensated ballasts: λ 0.85<br />

224