Technical Details – Emergency Lighting Modules for TC and T Lamps<br />

Additional information for optimising EMC<br />

Information on the installation of electronic ballasts for optimising EMC<br />

To ensure good radio interference suppression and the greatest possible operating<br />

safety, the following points should be observed when installing electronic ballasts:<br />

• Conductors between the EB and the lamp (HF conductors) must be kept short<br />

(reduction of electromagnetic interference). High-potential lamp conductors must<br />

be kept as short as possible, in particular with tubular lamps.<br />

Lamp conductors of this kind are labelled with an * in the wiring diagram on<br />

the type plate.<br />

• Mains and lamp conductors must be kept separate and if possible should not<br />

be laid in parallel to one another. The distance between HF and mains<br />

conductors should be as large as possible, ideally > 5 cm.<br />

(This prevents the induction of interference between the mains and lamp conductors.)<br />

• The mains conductor within the luminaire must be kept short (to reduce the<br />

induction of interference).<br />

• Devices must be properly earthed. EBs require secure contacts to the luminaire<br />

casing or must be earthed using a PE connection. This PE connection should be<br />

effected using an independent conductor to achieve better dissipation of the<br />

leak current. EMC improves at frequencies greater than 30 MHz.<br />

• The mains conductor must not be laid too close to the EB or the lamp (this is<br />

especially important in the event of through-wiring).<br />

• Mains and lamp conductors must not be crossed. Should this be impossible to avoid,<br />

conductors should be crossed at right angles to one another to avoid inducing<br />

interference between mains and HF conductors.<br />

• Should conductors be wired through metal parts, such conductors must always<br />

be additionally shielded (e.g. with an insulating sleeve or grommet).<br />

Maintenance With regard to system maintenance and control, care must be taken to ensure<br />

compliance with any ordinances and standards governing emergency lighting at the<br />

place of installation. Prior to opening lamp covers, the following procedure must be<br />

observed:<br />

1. Disconnect luminaires from the mains voltage.<br />

2. Remove cover.<br />

3. Disconnect battery from the emergency lighting module (disconnect the plug).<br />

<strong>VS</strong> recommends connecting control LEDs to be visible on the outside of emergency<br />

luminaires to enable simple and regular control of emergency luminaires and<br />

emergency lighting modules.<br />

Changing batteries<br />

Batteries need to be replaced if the operating period of luminaires falls short of 60 minutes<br />

in the case of 1-hour operation and 180 minutes for 3-hour operation, respectively.<br />

Emergency lighting modules have a status display for this purpose.<br />

Spent batteries must be replaced with the manufacturer's original batteries only. Furthermore,<br />

the polarity of the batteries must be strictly observed. The battery supply lines of<br />

the emergency lighting module are marked as follows:<br />

red = +; black = –<br />