Technical Details – Components for Discharge Lamps<br />

Assembly Instructions for Electronic Ballasts<br />

Assembly instructions for mounting and installing electronic ballasts<br />

for high-pressure discharge lamps<br />

Mandatory regulations<br />

DIN VDE 0100 Erection of low voltage installations<br />

EN 60598-1<br />

EN 61347-1<br />

EN 61347-2-12<br />

EN 55015<br />

Luminaires – part 1: general requirements and tests<br />

Operating devices for lamps – part 1: general and safety requirements<br />

Control gear for lamps; part 2-12: Particular requirements for d.c. or a.c. supplied electronic<br />

ballasts for discharge lamps (excluding fluorescent lamps)<br />

Limits and methods of measurement of radio disturbance characteristics of electrical lighting<br />

and similar equipment<br />

EN 61000-3-2 Electromagnetic Compatibility (EMC) – part 3: maximum values – main section part 2:<br />

maximum values for mains harmonics (device input current up to and including 16 A per conductor)<br />

EN 61547<br />

Installations for general lighting purposes – EMC immunity requirements<br />

Descriptions of <strong>VS</strong> EBs for discharge lamps<br />

The type designations for <strong>VS</strong> HID ballasts all follow the same pattern, as follows:<br />

EHXc 70 .326<br />

Electronic ballast for HID lamps Wattage Serial number<br />

Mechanical mounting<br />

Surface<br />

Firm, flat surface required to ensure good heat transfer. Avoid mounting on protruding surfaces.<br />

Mounting location<br />

Electronic ballasts must be protected against moisture and heat. Installation in outdoor luminaires:<br />

water protection rate of > 4 (e.g. IP54 required).<br />

Fastening<br />

Heat transfer<br />

Using M4 screws in the designated holes<br />

If the ballast is destined for installation in a luminaire, sufficient heat transfer must be ensured between<br />

the electronic ballast and the luminaire casing. Electronic ballasts should be mounted with the greatest<br />

possible clearance to heat sources or lamps. During operation, the temperature measure at the<br />

ballast's tc point must not exceed the specified maximum value.<br />

Supplement for independent electronic ballasts<br />

Mounting position<br />

Any position using the mounting tabs<br />

Clearance<br />

Surface<br />

Min. of 0.10 m from walls, ceilings and insulation<br />

Min. of 0.10 m from further electronic ballasts<br />

Min. of 0.25 m from sources of heat (lamp)<br />

Solid; EB must not be allowed to sink into insulation materials<br />