VRV IV sets the standard …again - Daikin
VRV IV sets the standard …again - Daikin
VRV IV sets the standard …again - Daikin
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
RTSYQ-PA<br />
RTSYQ14-16PA<br />
› First system in <strong>the</strong> industry developed for heating operation in low<br />
ambient conditions, making it suitable for single source heating<br />
› Extended operation range down to -25°C in heating<br />
› High COP values at low ambients thanks to <strong>the</strong> two stage<br />
compression technology (COP values of 3.0 and more at -10°C)<br />
› Improved comfort thanks to shorter defrost time<br />
› Shorter heat up time compared to <strong>standard</strong> <strong>VRV</strong>III heat pump<br />
› Easy installation thanks to automatic refrigerant<br />
charging operation, automatic test operation<br />
› Connectable to all <strong>VRV</strong> indoor units, ventilation and control systems<br />
Heating & Cooling<br />
Outdoor system<br />
RTSYQ10PA RTSYQ14PA RTSYQ16PA RTSYQ20PA<br />
System Outdoor unit module 1 RTSQ10PA RTSQ14PA RTSQ16PA RTSQ8PA<br />
Outdoor unit module 2 -<br />
RTSQ12PA<br />
Function unit BTSQ20P<br />
Capacity range HP<br />
10 14 16 20<br />
Cooling capacity Nom. kW<br />
28.0 (1) 40.0 (1) 45.0 (1) 56.0 (1)<br />
Heating capacity Nom. kW<br />
31.5 (2) / 28.0 (3) 45.0 (2) / 40.0 (3) 50.0 (2) / 45.0 (3) 63.0 (2) / 55.9 (3)<br />
Power input - 50Hz Cooling Nom. kW<br />
7.90 (1) 12.6 (1) 14.9 (1) 15.4 (1)<br />
Heating Nom. kW<br />
7.78 (2) / 8.18 (3) 11.4 (2) / 12.8 (3) 13.0 (2) / 15.0 (3) 15.4 (2) / 18.7 (3)<br />
EER<br />
3.54 (1) 3.17 (1) 3.02 (1) 3.64 (1)<br />
COP<br />
4.05 (2) / 3.42 (3) 3.95 (2) / 3.13 (3) 3.85 (2) / 3.00 (3) 4.09 (2) / 2.99 (3)<br />
Maximum number of connectable indoor units<br />
21 30 34 43<br />
Sound pressure level Cooling Max./Nom. dBA<br />
62/60 63/61 65/63<br />
Piping<br />
Liquid OD mm<br />
9.52 12.7 15.9<br />
connections Gas OD mm<br />
22.2 28.6<br />
Oil equalizing OD mm<br />
- 19.1<br />
Piping length OU - IU Max. m<br />
165<br />
Total piping length System Actual m<br />
500<br />
Level difference OU - IU m 50 (outdoor unit in highest position) / 40 (indoor unit in highest position)<br />
Current - 50Hz Maximum fuse amps (MFA) A<br />
25 35 40 50<br />
(1) Cooling: Indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m; function unit length: 6m; (2) Heating: Indoor temp. 20°CDB; outdoor temp. 7°CDB,6°CWB; equivalent piping length: 7.5m; level difference:<br />
0m; function unit length: 6m; (3) Heating: Indoor temp. 20°CDB; outdoor temp. -10°CWB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m<br />
146<br />
<strong>VRV</strong>III heat pump, optimised for heating<br />
Outdoor unit module<br />
BTSQ20P RTSQ8PA RTSQ10PA RTSQ12PA RTSQ14PA RTSQ16PA<br />
Dimensions Unit HeightxWidthxDepth mm 1,570x460x765 1,680x930x765 1,680x1,240x765<br />
Weight Unit kg<br />
110 205 257 338 344<br />
Sound power level Cooling Nom. dBA<br />
-<br />
Operation range Cooling Min.~Max. °CDB<br />
-5~43<br />
Heating Min.~Max. °CWB<br />
-25~15.5<br />
Refrigerant Type R-410A<br />
Power supply Phase/Frequency/Voltage Hz/V<br />
3~/50/380-415<br />
Current - 50Hz Maximum fuse amps (MFA) A<br />
20 25 35 40