RTSYQ-PA<br />

RTSYQ14-16PA<br />

› First system in <strong>the</strong> industry developed for heating operation in low<br />

ambient conditions, making it suitable for single source heating<br />

› Extended operation range down to -25°C in heating<br />

› High COP values at low ambients thanks to <strong>the</strong> two stage<br />

compression technology (COP values of 3.0 and more at -10°C)<br />

› Improved comfort thanks to shorter defrost time<br />

› Shorter heat up time compared to <strong>standard</strong> <strong>VRV</strong>III heat pump<br />

› Easy installation thanks to automatic refrigerant<br />

charging operation, automatic test operation<br />

› Connectable to all <strong>VRV</strong> indoor units, ventilation and control systems<br />

Heating & Cooling<br />

Outdoor system<br />

RTSYQ10PA RTSYQ14PA RTSYQ16PA RTSYQ20PA<br />

System Outdoor unit module 1 RTSQ10PA RTSQ14PA RTSQ16PA RTSQ8PA<br />

Outdoor unit module 2 -<br />

RTSQ12PA<br />

Function unit BTSQ20P<br />

Capacity range HP<br />

10 14 16 20<br />

Cooling capacity Nom. kW<br />

28.0 (1) 40.0 (1) 45.0 (1) 56.0 (1)<br />

Heating capacity Nom. kW<br />

31.5 (2) / 28.0 (3) 45.0 (2) / 40.0 (3) 50.0 (2) / 45.0 (3) 63.0 (2) / 55.9 (3)<br />

Power input - 50Hz Cooling Nom. kW<br />

7.90 (1) 12.6 (1) 14.9 (1) 15.4 (1)<br />

Heating Nom. kW<br />

7.78 (2) / 8.18 (3) 11.4 (2) / 12.8 (3) 13.0 (2) / 15.0 (3) 15.4 (2) / 18.7 (3)<br />

EER<br />

3.54 (1) 3.17 (1) 3.02 (1) 3.64 (1)<br />

COP<br />

4.05 (2) / 3.42 (3) 3.95 (2) / 3.13 (3) 3.85 (2) / 3.00 (3) 4.09 (2) / 2.99 (3)<br />

Maximum number of connectable indoor units<br />

21 30 34 43<br />

Sound pressure level Cooling Max./Nom. dBA<br />

62/60 63/61 65/63<br />

Piping<br />

Liquid OD mm<br />

9.52 12.7 15.9<br />

connections Gas OD mm<br />

22.2 28.6<br />

Oil equalizing OD mm<br />

- 19.1<br />

Piping length OU - IU Max. m<br />

165<br />

Total piping length System Actual m<br />

500<br />

Level difference OU - IU m 50 (outdoor unit in highest position) / 40 (indoor unit in highest position)<br />

Current - 50Hz Maximum fuse amps (MFA) A<br />

25 35 40 50<br />

(1) Cooling: Indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m; function unit length: 6m; (2) Heating: Indoor temp. 20°CDB; outdoor temp. 7°CDB,6°CWB; equivalent piping length: 7.5m; level difference:<br />

0m; function unit length: 6m; (3) Heating: Indoor temp. 20°CDB; outdoor temp. -10°CWB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m<br />

146<br />

<strong>VRV</strong>III heat pump, optimised for heating<br />

Outdoor unit module<br />

BTSQ20P RTSQ8PA RTSQ10PA RTSQ12PA RTSQ14PA RTSQ16PA<br />

Dimensions Unit HeightxWidthxDepth mm 1,570x460x765 1,680x930x765 1,680x1,240x765<br />

Weight Unit kg<br />

110 205 257 338 344<br />

Sound power level Cooling Nom. dBA<br />

-<br />

Operation range Cooling Min.~Max. °CDB<br />

-5~43<br />

Heating Min.~Max. °CWB<br />

-25~15.5<br />

Refrigerant Type R-410A<br />

Power supply Phase/Frequency/Voltage Hz/V<br />

3~/50/380-415<br />

Current - 50Hz Maximum fuse amps (MFA) A<br />

20 25 35 40