VRV IV sets the standard …again - Daikin
VRV IV sets the standard …again - Daikin
VRV IV sets the standard …again - Daikin
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
VKM-G(M)<br />
› Creates a high quality indoor environment by pre conditioning incoming<br />
fresh air<br />
› Humidification of <strong>the</strong> incoming air maintains a comfortable indoor<br />
humidity level, even during heating<br />
› Energy saving ventilation by recovery of indoor unit heat/cold<br />
› Ideal solution for shops, restaurants or offices requiring maximum floor<br />
space for furniture, decorations and fittings<br />
› Free cooling when outdoor temperature is below indoor temperature<br />
(eg. during night time)<br />
› Can be used as stand alone unit or integrated in <strong>the</strong> <strong>VRV</strong> system<br />
› Wide range of units: air flow rate from 150 up to 2,000 m³/h<br />
› Specially developed heat exchange element with High Efficiency Paper (HEP)<br />
› No drain piping needed<br />
› Can operate in over- and under pressure<br />
Ventilation & DX coil<br />
Power input - 50Hz Heat exchange mode Nom. Ultra high kW<br />
Bypass mode Nom. Ultra high kW<br />
Fresh air<br />
conditioning load<br />
VKM80-100G<br />
Cooling kW<br />
Heating kW<br />
Temperature exchange efficiency - 50Hz Ultra high %<br />
Enthalpy exchange Cooling Ultra high %<br />
efficiency - 50Hz Heating Ultra high %<br />
187<br />
Heat reclaim ventilation,<br />
humifidication and air processing<br />
VKM50G VKM80G VKM100G<br />
0.560 0.620 0.670<br />
0.560 0.620 0.670<br />
4.71 7.46 9.12<br />
5.58 8.79 10.69<br />
76 78 74<br />
64 66 62<br />
67 71 65<br />
Operation mode Heat exchange mode / Bypass mode / Fresh-up mode<br />
Heat exchange system Air to air cross flow total heat (sensible + latent heat) exchange<br />
Heat exchange element Specially processed non-flammable paper<br />
Dimensions Unit HeightxWidthxDepth mm<br />
387x1,764x832 387x1,764x1,214<br />
Weight Unit kg<br />
96 109 114<br />
Fan-Air flow rate Heat exchange mode Ultra high m³/h<br />
500 750 950<br />
- 50Hz<br />
Bypass mode Ultra high m³/h<br />
500 750 950<br />
Fan-External static pressure - 50Hz Ultra high Pa<br />
Sound pressure Heat exchange mode Ultra high dBA<br />
38 / 38.5 / 39 40 / 41 / 41.5 40 / 40.5 / 41<br />
level - 50Hz Bypass mode Ultra high dBA<br />
38 / 38.5 / 39 40 / 41 / 41.5 40 / 40.5 / 41<br />
Operation range Around unit °CDB<br />
0°C~40°CDB, 80% RH or less<br />
Supply air °CDB<br />
-15°C~40°CDB, 80% RH or less<br />
Return air °CDB<br />
0°C~40°CDB, 80% RH or less<br />
Connection duct diameter mm<br />
200 250<br />
Piping<br />
Liquid OD mm<br />
6.35<br />
connections Gas OD mm<br />
12.7<br />
Drain PT3/4 external thread<br />
Power supply Phase/Frequency/Voltage Hz/V<br />
1~/50/220-240<br />
Current Maximum fuse amps (MFA) A<br />
15<br />
Ventilation, DX coil & humidification<br />
VKM50GM VKM80GM VKM100GM<br />
Power input - 50Hz Heat exchange mode Nom. Ultra high kW<br />
0.560 0.620 0.670<br />
Bypass mode Nom. Ultra high kW<br />
0.560 0.620 0.670<br />
Fresh air<br />
Cooling kW<br />
4.71 7.46 9.12<br />
conditioning load Heating kW<br />
5.58 8.79 10.69<br />
Temperature exchange efficiency - 50Hz Ultra high %<br />
76 78 74<br />
Enthalpy exchange Cooling Ultra high %<br />
64 66 62<br />
efficiency - 50Hz Heating Ultra high %<br />
67 71 65<br />
Operation mode Heat exchange mode / Bypass mode / Fresh-up mode<br />
Heat exchange system Air to air cross flow total heat (sensible + latent heat) exchange<br />
Heat exchange element Specially processed non-flammable paper<br />
Humidifier System Natural evaporating type<br />
Dimensions Unit HeightxWidthxDepth mm<br />
387x1,764x832 387x1,764x1,214<br />
Weight Unit kg<br />
102 120 125<br />
Fan-Air flow rate Heat exchange mode Ultra high m³/h<br />
500 750 950<br />
- 50Hz<br />
Bypass mode Ultra high m³/h<br />
500 750 950<br />
Fan-External static pressure - 50Hz Ultra high Pa<br />
160 140 110<br />
Sound pressure Heat exchange mode Ultra high dBA<br />
37 / 37.5 / 38 38.5 / 39 / 40 39 / 39.5 / 40<br />
level - 50Hz Bypass mode Ultra high dBA<br />
37 / 37.5 / 38 38.5 / 39 / 40 39 / 39.5 / 40<br />
Operation range Around unit °CDB<br />
0°C~40°CDB, 80% RH or less<br />
Supply air °CDB<br />
-15°C~40°CDB, 80% RH or less<br />
Return air °CDB<br />
0°C~40°CDB, 80% RH or less<br />
Connection duct diameter mm<br />
200 250<br />
Piping<br />
Liquid OD mm<br />
6.35<br />
connections Gas OD mm<br />
12.7<br />
Water supply mm<br />
6.4<br />
Drain PT3/4 external thread<br />
Power supply Phase/Frequency/Voltage Hz/V<br />
1~/50/220-240<br />
Current Maximum fuse amps (MFA) A<br />
15