VRV IV sets the standard …again - Daikin
VRV IV sets the standard …again - Daikin
VRV IV sets the standard …again - Daikin
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
EMRQ-A<br />
EMRQ8-16A<br />
› Low energy bills and low CO 2 emissions<br />
› Easy installation and maintenance<br />
› Integrated heat recovery system<br />
› The ultimate heating solution for residential and commercial<br />
applications based on air to water heat pump technology<br />
› Customised to meet your building’s needs: up to 10<br />
indoor units can be connected to 1 outdoor unit<br />
Heat recovery<br />
(1) Condition: Ta=7°CDB/6°CWB, 100% connection ratio (2) Condition: Ta=35°CDB, 100% connection ratio<br />
<strong>Daikin</strong> Al<strong>the</strong>rma Flex Type - outdoor unit<br />
Outdoor unit<br />
EMRQ8A EMRQ10A EMRQ12A EMRQ14A EMRQ16A<br />
Heating capacity Nom. kW<br />
22.4 (1) 28 (1) 33.6 (1) 39.2 (1) 44.8 (1)<br />
Cooling capacity Nom. kW<br />
20 (2) 25 (2) 30 (2) 35 (2) 40 (2)<br />
Dimensions Unit HeightxWidthxDepth mm<br />
1,680x1,300x765<br />
Weight Unit kg<br />
331 339<br />
Operation range Heating Min.~Max. °CWB<br />
-15~20<br />
Domestic hot water Ambient Min.~Max. °CDB<br />
-15~35<br />
Cooling Min.~Max. °CDB<br />
10~43<br />
Refrigerant Type R-410A<br />
Piping<br />
Liquid OD mm<br />
9.52 12.7<br />
connections Suction OD mm<br />
19.1 22.2 28.6<br />
High and low pressure gas OD mm<br />
15.9 19.1 22.2<br />
Piping length OU - IU Max. m<br />
100<br />
System Equivalent m<br />
120<br />
Total piping length System Actual m<br />
300<br />
Sound power level Heating Nom. dBA<br />
78 80 83 84<br />
Sound pressure level Heating Nom. dBA<br />
58 60 62 63<br />
Power supply Name/Phase/Frequency/Voltage<br />
Y1/3~/50/380-415<br />