Heat recovery<br />
Heating & Cooling<br />
Outdoor unit<br />
RWEYQ8P RWEYQ10P<br />
Capacity range HP<br />
8 10<br />
Cooling capacity Nom. kW<br />
22.4 26.7<br />
Heating capacity Nom. kW<br />
25.0 31.5<br />
Power input - 50Hz Cooling Nom. kW<br />
4.55 6.03<br />
Heating Nom. kW<br />
4.24 6.05<br />
EER<br />
4.89 4.14<br />
COP<br />
5.81 5.08<br />
Maximum number of connectable indoor units<br />
17 21<br />
Indoor index Min.<br />
100 125<br />
connection Nom.<br />
200 250<br />
Max.<br />
260 325<br />
Dimensions Unit HeightxWidthxDepth mm<br />
1,000x780x550<br />
Weight Unit kg<br />
149 150<br />
Sound power level Cooling Nom. dBA<br />
-<br />
Sound pressure level Cooling Nom. dBA<br />
50 51<br />
Operation range Inlet water Cooling Min.~Max. °CDB<br />
10~45<br />
temperature Heating Min.~Max. °CWB<br />
10~45<br />
Refrigerant Type R-410A<br />
Piping<br />
Liquid OD mm<br />
9.52<br />
connections Gas OD mm<br />
19.1 (1) 22.2 (1)<br />
Discharge gas OD mm<br />
15.9 (2) / 19.1 (3) 19.1 (2) / 22.2 (3)<br />
Water Inlet/Outlet PT1 1/4B internal thread/PT1 1/4B internal thread<br />
Piping length OU - IU Max. m<br />
120<br />
Total piping length System Actual m<br />
300<br />
Level difference OU - IU m 50 (outdoor unit in highest position) / 40 (indoor unit in highest position)<br />
Power supply Phase/Frequency/Voltage Hz/V<br />
3~/50/380-415<br />
Current - 50Hz Maximum fuse amps (MFA) A<br />
25<br />
(1) In case of heat pump system, gas pipe is not used (2) In case of heat recovery system (3) In case of heat pump system<br />
Outdoor system<br />
RWEYQ16P RWEYQ18P RWEYQ20P RWEYQ24P RWEYQ26P RWEYQ28P RWEYQ30P<br />
System Outdoor unit module 1 RWEYQ8P RWEYQ10P RWEYQ8P RWEYQ10P<br />
Outdoor unit module 2 RWEYQ8P RWEYQ10P RWEYQ8P RWEYQ10P<br />
Outdoor unit module 3 -<br />
RWEYQ8P RWEYQ10P<br />
Capacity range HP<br />
16 18 20 24 26 28 30<br />
Cooling capacity Nom. kW<br />
44.8 49.1 53.4 67.2 71.5 75.8 80.1<br />
Heating capacity Nom. kW<br />
50.0 56.5 63.0 75.0 81.5 88.0 94.5<br />
Power input - 50Hz Cooling Nom. kW<br />
9.10 10.6 12.1 13.7 15.1 16.6 18.1<br />
Heating Nom. kW<br />
8.48 10.3 12.1 12.7 14.5 16.3 18.2<br />
EER<br />
4.92 4.63 4.41 4.91 4.74 4.57 4.43<br />
COP<br />
5.87 5.48 5.21 5.91 5.62 5.40 5.19<br />
Maximum number of connectable indoor units<br />
34 36<br />
Sound pressure level Cooling Nom. dBA<br />
53 54 55 56<br />
Piping<br />
Liquid OD mm<br />
12.7 15.9 19.1<br />
connections Gas OD mm<br />
28.6 (1) 34.9 (1)<br />
Discharge gas OD mm 22.2 (2) / 28.6 (3) 22.2 (2) / 28.6 (3) 22.2 (2) / 28.6 (3) 28.6 (2) / 34.9 (3) 28.6 (2) / 34.9 (3) 28.6 (2) / 34.9 (3) 28.6 (2) / 34.9 (3)<br />
Piping length OU - IU Max. m<br />
120<br />
Total piping length System Actual m<br />
300<br />
Level difference OU - IU m 50 (outdoor unit in highest position) / 40 (indoor unit in highest position)<br />
Current - 50Hz Maximum fuse amps (MFA) A<br />
35 45<br />
(1) In case of heat pump system, gas pipe is not used (2) In case of heat recovery system (3) In case of heat pump system<br />
159