REYAQ-P<br />

› Temperature control, fresh air provision, Biddle air curtains and<br />

hot water production all integrated in a single system<br />

› Heat recovery maximises energy efficiency with COPs of up to 8 possible!<br />

› Free heating provided by transferring heat from areas<br />

requiring cooling to areas requiring heating or hot water<br />

› Perfect comfort: simultaneous heating and cooling<br />

› Compact size leaves maximum floorspace<br />

› Fits any building with ei<strong>the</strong>r outdoor or indoor installation<br />

possible (high external static pressure up to 78.4Pa)<br />

› The ability to control each conditioned zone individually keeps<br />

<strong>VRV</strong> system running costs to an absolute minimum<br />

› Spread your installation cost by phased installation<br />

› Wide range of indoor units: 15 different models in a total of 76 variations<br />

Heat recovery<br />

(1) Field setting<br />

REYAQ-P<br />

<strong>VRV</strong>III heat recovery, with connection to heating<br />

only hydrobox<br />

Outdoor unit<br />

REYAQ10P REYAQ12P REYAQ14P REYAQ16P<br />

Capacity range HP<br />

10 12 14 16<br />

Cooling capacity Nom. kW<br />

28 33.5 40 45<br />

Heating capacity Nom. kW<br />

31.5 37.5 45 50<br />

Power input - 50Hz Cooling Nom. kW<br />

7.09 8.72 11.4 14.1<br />

Heating Nom. kW<br />

7.38 8.84 11.0 12.8<br />

EER<br />

3.95 3.84 3.51 3.19<br />

COP<br />

4.27 4.24 4.09 3.91<br />

Maximum number of connectable indoor units<br />

21 26 30 34<br />

Indoor index Min.<br />

125 150 175200 connection Nom.<br />

250 300 350 400<br />

Max.<br />

325 390 455 520<br />

Dimensions Unit HeightxWidthxDepth mm<br />

1,680x1,300x765<br />

Weight Unit kg<br />

331 339<br />

Sound power level Cooling Nom. dBA<br />

78 80 83 84<br />

Sound pressure level Cooling Nom. dBA<br />

58 60 62 63<br />

Operation range Cooling Min.~Max. °CDB<br />

-5~43<br />

Heating Min.~Max. °CWB<br />

-20~15.5<br />

Hot water<br />

Space heating Min.~Max. °CDB<br />

-20~20 / 24 (1) -20~20 / 24 (1) -20~20 / 24 (1) -20~20 / 24 (1)<br />

production<br />

Domestic hot water Min.~Max. °CDB<br />

-20~43<br />

Refrigerant Type R-410A<br />

Piping<br />

Liquid OD mm<br />

9.52 12.7<br />

connections Gas OD mm<br />

22.2 28.6<br />

Discharge gas OD mm<br />

19.1 22.2<br />

Piping length OU - IU Max. m<br />

100<br />

Total piping length System Actual m<br />

300<br />

Level difference OU - IU m 40 (outdoor unit in highest position) / 40 (indoor unit in highest position)<br />

Power supply Phase/Frequency/Voltage Hz/V<br />

3~/50/380-415<br />

Current - 50Hz Maximum fuse amps (MFA) A<br />

25 40<br />

151