TECHNICAL INFORMATION<br />

Pipelines<br />

distances between supports<br />

Maximum recommended fastening distances for pipelines according to DIN <strong>EN</strong> 806 part 4<br />

Carbon steel system pipe<br />

GEBERIT Mapress<br />

DIN <strong>EN</strong> 10305<br />

Spacings acc. to<br />

manufacturer<br />

[m]<br />

DN<br />

[NW]<br />

Nominal dimension d x s<br />

[mm]<br />

Befestigung<br />

horizontal<br />

Empfehlung<br />

GEBERIT<br />

10 12 x 1.2 1.00 1.50<br />

12 15 x 1.2 1.20 1.50<br />

15 18 x 1.2 1.20 1.50<br />

20 22 x 1.2 1.80 2.50<br />

25 28 x 1.5 1.80 2.50<br />

32 35 x 1.5 2.40 3.50<br />

40 42 x 1.5 2.40 3.50<br />

50 54 x 1.5 2.70 3.50<br />

65 76.1 x 2.0 3.00 5.00<br />

80 88.9 x 2.0 3.00 5.00<br />

100 108 x 2.0 3.00 5.00<br />

Maximum recommended fastening distances for pipelines according to VdS CEA 4001 for sprinkler systems<br />

DN<br />

[NW]<br />

Carbon steel system pipe<br />

GEBERIT Mapress<br />

1.0215 galvanised inside and outside<br />

Nominal dimension d x s<br />

[mm]<br />

Spacings acc. to<br />

manufacturer<br />

[m]<br />

20 22 x 1.5 2.00<br />

25 28 x 1.5 2.00<br />

32 35 x 1.5 2.00<br />

40 42 x 1.5 2.00<br />

50 54 x 1.5 2.00<br />

65 76.1 x 2.0 2.00<br />

80 88.9 x 2.0 2.00<br />

100 108 x 2.0 2.00<br />

!<br />

Any relevant information from the pipe manufacturer is to be taken into account.<br />