TECHNICAL INFORMATION<br />

fire protection<br />

certified F90<br />

Plug characteristic values for screws for concrete<br />

Type Multi-Mont i ® MMS for fastenings in concrete, galvanised<br />

Permissible loads 1) for the use in concrete for redundant, non-load-bearing systems in<br />

concrete, concrete strength class C20/25 (B25) in accordance with European Technical<br />

Assessment ETA-15/0785<br />

Characteristic values<br />

Dim.<br />

Size 7.5 10<br />

Total anchoring depth hnom [mm] 25 35 55 50<br />

Permissible tensile load of cracked concrete 2) Nperm [kN] 0.49 1.22 2.44 2.44<br />

Permissible tensile load of non-cracked concrete 2) Nperm [kN] 0.97 2.44 2.44 2.44<br />

Permissible transverse load of cracked concrete 2) Vperm [kN] 1.07 2.25 4.78 5.99<br />

Permissible transverse load of non-cracked concrete 2) Vperm [kN] 1.54 3.22 5.21 8.12<br />

Minimum axial spacing smin [mm] 30 35 35 35<br />

Minimum edge spacing cmin [mm] 30 30 30 35<br />

Component width hmin [mm] 80 80 80 80<br />

Installation and plug characteristic values<br />

Size 7.5 10<br />

Total anchoring depth hnom [mm] 25 35 55 50<br />

Drilled hole depth h1 ≥ [mm] 30 40 60 60<br />

Nominal drill diameter do [mm] 6 6 6 8<br />

Electric tangential impact wrench max. power output Tinst [Nm] 60 120 120 250<br />

according to specifications of manufacturer<br />

Clearance hole in the add-on part df [mm] 9 9 9 12.5<br />

The entire assessment must be taken into account when dimensioning.<br />

Static or quasi-static stress.<br />

See the European Technical Assessment ETA-15/0785 for additional installation and plug characteristic values.<br />

1)<br />

Only for the <strong>attachment</strong> of redundant systems.<br />

2)<br />

According to <strong>EN</strong> 1992-4,7.2.1.3 and 7.2.1.4 and ETA-15/0785 partial safety coefficients on the resistance side of<br />

yM = 1.5 and on the action side of yG = 1.35 were taken into account.<br />

All the specifications in the European Technical Assessment (ETA) must be taken into account when dimensioning.<br />

Type P Type ST Type I<br />

Type MS<br />

Type SS<br />

07/<strong>2023</strong><br />

8/34 © Müpro - progress and quality