TECHNICAL INFORMATION<br />

fire protection<br />

certified F90<br />

Plug characteristic values for steel plugs<br />

with and without collar, galvanised<br />

Permissible loads for the use of multiple fastening of non-load bearing systems in<br />

concrete, strength class C20/25 (B25) in accordance with Assessment ETA-05/0161<br />

Plug (thread) Dim. M6 x 30 M8 x 25 M8 x 30 M8 x 40 M10 x 25 M10 x 30 M10 x 40 M12 x 25 M12 x 50 M16 x 65<br />

Permissible tensile load 1) perm. N [kN] 1.2 1.9 1.7 2.0 2.1 2.0 2.0 2.1 2.4 6.3<br />

Permissible bending moment 1) perm. M [Nm] 2.6 6.4 6.4 6.4 12.8 12.8 12.8 22.2 22.2 56.9<br />

Effective anchoring depth hef [mm] 30 25 30 40 25 30 40 25 50 65<br />

Characteristic pitch scr, N [mm] 130 75 180 210 75 230 170 75 170 400<br />

Characteristic edge clearance ccr, N [mm] 65 38 90 105 38 115 85 38 85 200<br />

Min. pitch smin [mm] 55 50 60 80 60 100 100 100 120 150<br />

Min. edge clearance cmin [mm] 95 100 95 95 100 115 135 110 165 200<br />

Min. building element thickness hmin1 [mm] 100 80 100 100 80 120 120 80 130 160<br />

Standard building element<br />

thickness<br />

hmin2 [mm] 100 100 100 100 100 120 120 100 130 160<br />

1)<br />

With screw, strength class 4.6<br />

Installation and plug characteristic values<br />

Plug (thread) Dim. M6 x 30 M8 x 25 M8 x 30 M8 x 40 M10 x 25 M10 x 30 M10 x 40 M12 x 25 M12 x 50 M16 x 65<br />

Nominal drill diameter d0 [mm] 8 10 10 10 12 12 12 15 15 20<br />

Drilled hole depth h1 ≥ [mm] 30 25 30 40 25 30 40 25 50 65<br />

Torque for anchoring Tinst [Nm] 4 8 8 8 15 15 15 35 35 60<br />

Clearance hole in the<br />

df [mm] 7 9 9 9 12 12 12 14 14 18<br />

add-on part<br />

Minimum screwing depth Lsd [mm] 7 8 9 9 10 10 11 12 13 18<br />

Maximum screwing depth Lth [mm] 13 12 13 20 12 12 15 12 18 23<br />

Use as multiple fastening of non-load bearing systems according to ETAG 001, part 6.<br />

The total safety coefficient (γM and γF) in accordance with ETAG is included.<br />

The max. permitted load for each <strong>attachment</strong> point can be below the permitted load of the anchor, depending on national<br />

regulations. The permitted loads for each <strong>attachment</strong> point are regulated by ETAG 001, part 6 for the different countries.<br />

All the specifications in the European Technical Assessment ETA-05/0161 need to be taken into account.<br />

Loads under fire exposure (C20/25 to C50/60)<br />

Plug (thread) Dim. M6 x 30 M8 x 25 M8 x 30 M8 x 40 M10 x 25 M10 x 30 M10 x 40 M12 x 25 M12 x 50 M16 x 65<br />

Permissible loads R30 perm. F [kN] 0.4 0.6 0.9 1.1 0.6 0.9 1.5 0.6 1.5 4.0<br />

Permissible loads R60 perm. F [kN] 0.3 0.6 0.9 0.9 0.6 0.9 1.5 0.6 1.5 4.0<br />

Permissible loads R90 perm. F [kN] 0.3 0.6 0.6 0.6 0.6 09 1.1 0.6 1.5 3.0<br />

Permissible loads R120 perm. F [kN] 0.3 0.5 0.5 0.5 0.5 0.7 0.9 0.5 1.2 2.4<br />

Characteristic pitch scr, Fi [mm] 130 100 180 210 100 170 170 100 200 400<br />

Characteristic edge clearance ccr, Fi [mm] 65 50 90 105 50 85 85 50 100 200<br />

Loads apply for screws, strength class ≥ 4.6.<br />

Plug arrangement and component dimensions<br />

07/<strong>2023</strong><br />

© Müpro - progress and quality<br />