TECHNICAL INFORMATION<br />

fire protection<br />

certified<br />

CONSTRUCTION SUPERVISION<br />

APPROVED<br />

CERTIFIED QUALITY<br />

Plug characteristic values for<br />

gas concrete under cut anchor<br />

Permissible loads under fire stress in accordance with DIN 4102-2 in aerated concrete,<br />

strength class ≥ P 3.3 in the intermediate area of lightweight ceiling cladding and false<br />

ceilings in accordance with DIN 18168<br />

Plug (size) Dim. M8 M10 M8 M10 M12<br />

Fire resistance class For all load directions GBH A GBH A GBH I GBH I GBH I<br />

R 30 Permissible load Fperm [kN] 0.45 0.80 0.45 0.80 0.80<br />

R 60 Permissible load Fperm [kN] 0.45 0.80 0.45 0.80 0.80<br />

R 90 Permissible load Fperm [kN] 0.45 0.80 0.45 0.80 0.80<br />

R 120 Permissible load Fperm [kN] 0.35 0.75 0.35 0.75 0.75<br />

R 30 to 120 Minimum component thickness hmin ≥ [mm] 175 175 175 175 175<br />

Minimum intermediate spacing amin ≥ [mm] 600 200 600 600 600<br />

Minimum axial spacing smin ≥ [mm] 100 100 100 100 100<br />

Minimum edge spacing cmin ≥ [mm] 150 150 150 150 150<br />

All information specified in the DIBt general technical approval must be taken into consideration for dimensioning.<br />

See general technical approval Z-21.1-1525 for additional installation and plug characteristic values.<br />