Engineering System - Siemens Automation and Drives Group
Engineering System - Siemens Automation and Drives Group
Engineering System - Siemens Automation and Drives Group
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
SIMATIC PCS 7 BOX supports not only the distributed I/O devices<br />
of the ET 200 range with an extensive selection of cost-effective<br />
signal <strong>and</strong> function modules but also the connection of<br />
intelligent field/process devices on PROFIBUS PA. The process<br />
I/Os are connected through the two PROFIBUS DP ports of the<br />
slot CPU. As SIMATIC PDM can only access field devices on the<br />
PROFIBUS DP through the onboard communications processor<br />
CP 5611, an additional cross connection between the DP port<br />
<strong>and</strong> CP 5611 is required to use SIMATIC PDM . A plug required<br />
for this purpose is supplied with the SIMATIC PCS 7 BOX.<br />
Configuration modifications during operation (CiR) are not yet<br />
supported by the current CPU WinAC Slot 416. However, plans<br />
to include this functionality in future WinAC Slot CPUs are currently<br />
in the pipeline.<br />
In a plant network with other SIMATIC PCS 7 system components<br />
such as AS, OS, ES or BATCH <strong>and</strong> MES applications, bus<br />
communication is implemented through the Ethernet interface<br />
integrated in the SIMATIC PCS 7 BOX. An additional CP 1512 is<br />
required (see "Accessories") for connecting to the SIMATIC<br />
PCS 7 terminal bus (OS-LAN).<br />
SIMATIC PCS 7 BOX is available in the form of two product bundles:<br />
as a preinstalled SIMATIC PCS 7 complete system with AS, ES<br />
<strong>and</strong> OS functionality for up to 250 process objects (POs) / 8 K<br />
OS variables<br />
as a preinstalled SIMATIC PCS 7 runtime system with AS <strong>and</strong><br />
OS functionality for up to 250 process objects (POs) / 8 K OS<br />
variables<br />
These can be further exp<strong>and</strong>ed using the following add-on/expansion<br />
components (see also Chapter "ES/OS/Batch/IT basic<br />
devices" <strong>and</strong> the catalog "PC-based <strong>Automation</strong>"):<br />
SIMATIC PCS 7 Power Packs for up to 2,000 POs / 64 K OS<br />
variables<br />
SIMATIC PDM Package for PCS 7<br />
CP 1512 for connecting to the OS-LAN (SIMATIC PCS 7 terminal<br />
bus) of a SIMATIC PCS 7 plant network<br />
TK 200 st<strong>and</strong>ard keyboard<br />
Display <strong>and</strong> CRT monitors for office <strong>and</strong> industrial environments<br />
SITOP power supply 230 V AC / 24 V DC<br />
SITOP power DC-UPS module 15 A with RS 232 interface<br />
DC-UPS software for the further processing of signals sent<br />
from the DC-UPS module using the RS 232 interface on the PC<br />
(state visualization <strong>and</strong> the definition of reactions to different<br />
operating states of the DC-UPS module), can be used with<br />
Windows NT, 2000 <strong>and</strong> XP; freeware for downloading at<br />
http://www.siemens.com/sitop<br />
SITOP power battery module 24 V DC /20 A/7 Ah for DC-UPS<br />
module 15 A<br />
■ Technical specifications<br />
SIMATIC PCS 7 BOX<br />
SIMATIC PCS 7 BOX<br />
Industrial PC: SIMATIC Box PC 620<br />
CPU Intel Pentium III 1.26 GHz<br />
Main memory 1 Gbyte<br />
Second Level Cache 512 Kbyte<br />
Hard disk memory 80 Gbyte<br />
Diskette drive 1.44 Mbyte<br />
DVD-ROM/CD-RW Combo drive 8/8/24x<br />
Graphics UXGA LCD controller on AGP<br />
bus, 1280 x 1024 at 85 Hz<br />
Ethernet integrated Ethernet interface<br />
10/100 Mbit/s (RJ45)<br />
PROFIBUS DP 12 Mbit/s (floating, CP 5611-compatible)<br />
USB 2 terminals (high current)<br />
Expansions 1 CardBus slot for PCMCIA Typ III<br />
PC card<br />
Power supply 24 V DC<br />
Operating system Microsoft Windows 2000 Professional<br />
<strong>Automation</strong>: slot PLC module<br />
CPU WinAC Slot 416 V3.4<br />
Main memory 1.6 + 1.6 Mbyte (integrated)<br />
Loading memory 256 Kbyte<br />
Memory card 2 Mbyte RAM (installed)<br />
Processing times Binary comm<strong>and</strong>: 0.08 µs,<br />
IEEE floating point: 0.48 µs<br />
PROFIBUS DP PROFIBUS DP <strong>and</strong><br />
PROFIBUS DP/MPI interface<br />
onboard<br />
Connectable distributed I/Os ET 200M, ET 200iS, ET 200S,<br />
PROFIBUS DP st<strong>and</strong>ard slaves,<br />
PROFIBUS PA devices (using<br />
DP/PA link or DP-PA coupler)<br />
Dimensions PCI plug-in card (3/4 long)<br />
Power supply Power supply extension board<br />
independent of PC;<br />
external power supply 24 V DC<br />
<strong>and</strong> battery buffer<br />
Operation <strong>and</strong> visualization<br />
Software PCS 7 OS Software Single Station<br />
V6.0 (preinstalled)<br />
Licenses 250 POs/RT 8K variables<br />
(extendable to 2000 POs/RT 64K<br />
per PowerPack)<br />
<strong>Engineering</strong><br />
Software PCS 7 <strong>Engineering</strong> Software V6.0<br />
(preinstalled)<br />
Licenses AS/OS for 250 POs/RC 8K<br />
(extendable to 2000 POs/RC 64K<br />
per Power Pack)<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
3/3<br />
3