9<br />
Communication<br />
PROFIBUS DP<br />
Plastic fiber optic cable<br />
■ Overview<br />
■ Design<br />
SIMATIC NET plastic fiberoptic cables can be used for the con- Different versions of plastic FOC are available:<br />
struction of optical PROFIBUS DP networks for indoor applications.<br />
Plastic fiberoptic cables are easy to assemble on-site with<br />
2 x 2 simplex connectors. The maximum cable length between<br />
two DP devices is 50 m.<br />
PROFIBUS plastic fiber optic st<strong>and</strong>ard cable<br />
rugged round cable with purple PVC outer casing <strong>and</strong> Kevlar<br />
tension-relief elements as well as plastic fibers with rugged<br />
polyamide inner casing. For indoor applications with cable<br />
Using SIMATIC PCS 7, plastic fiberoptic cables are an alterna- lengths up to 50 m<br />
tive for automation system connections of ET 200M with only failsafe<br />
I/O modules when compliance with SIL 3 is dem<strong>and</strong>ed for<br />
the failsafe application. Plastic fiberoptic cables are then used to<br />
connect the ET 200Ms through Optical Bus Terminals (OBT) to<br />
the electrical bus cable of the PROFIBUS DP. The advantage of<br />
this configuration is that it eliminates the disconnecting module<br />
for decoupling the signal between the IM <strong>and</strong> the failsafe mod-<br />
PROFIBUS plastic fiberoptic, duplex core<br />
flat double core with PVC inner casing <strong>and</strong> no outer casing, for<br />
indoor applications with low mechanical loads, e.g. inside<br />
cabinets. Cable length up to 50 m.<br />
To use the plastic FOC, following items are required in addition<br />
to the OBT:<br />
ules, which is otherwise obligatory for the direct electrical con- Simplex connector/polishing set (set with 100 simplex connection<br />
of the ET 200M (only failsafe modules in a rack with nectors <strong>and</strong> 5 polishing sets)<br />
IM 153-2).<br />
Stripping tool set for removing the outer casing <strong>and</strong> core casing<br />
Plug adapter for using simplex connectors with the integrated<br />
FO interfaces (e.g. IM 153-2 FO)<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PROFIBUS OBT<br />
Optical bus terminal for connecting<br />
a PROFIBUS station or an<br />
RS 485 segment without integrated<br />
optical interface to the<br />
optical PROFIBUS; without simplex<br />
connector<br />
6GK1 500-3AA00<br />
PROFIBUS Plastic Fiber Optic,<br />
St<strong>and</strong>ard Cable<br />
Robust round cable with 2 plastic<br />
fiberoptic cores, PVC external<br />
sheath <strong>and</strong> PA internal sheath,<br />
without connectors, for indoor<br />
6XV1 821-0AH10 B)<br />
use, sold by the meter<br />
OBT for PROFIBUS DP<br />
PROFIBUS Plastic Fiber Optic, 6XV1 821-2AN50 B)<br />
With the OBT (Optical Bus Terminal) for PROFIBUS it is possible Duplex Core<br />
to connect a PROFIBUS DP station with an integrated optical in- Plastic fiberoptic cable with<br />
terface to an RS 485 segment or a PROFIBUS DP station without 2 cores, PVC sheath, without con-<br />
an integrated optical interface. Plastic fiberoptic cables can be<br />
used for the optical connection between the PROFIBUS DP station<br />
with an integrated optical interface <strong>and</strong> the OBT.<br />
nectors, for use in environments<br />
with low mechanical stress, 50-m<br />
ring<br />
PROFIBUS Plastic Fiber Optic,<br />
Simplex Connector/<br />
Polishing Set<br />
100 simplex connectors <strong>and</strong><br />
5 polishing sets for assembling<br />
PROFIBUS plastic fiberoptic<br />
cables for the optical PROFIBUS<br />
DP<br />
6GK1 901-0FB00-0AA0 B)<br />
PROFIBUS Plastic Fiber Optic,<br />
Stripping Tool Set<br />
To remove the external or core<br />
sleeve of plastic fiberoptic cables<br />
6GK1 905-6PA10 B)<br />
Connection Adapter<br />
Pack of 50, for using simplex connectors<br />
with the integrated FO<br />
interfaces (e.g. IM 153-2 FO); for<br />
25 modules<br />
6ES7 195-1BE00-0XA0<br />
9/12<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H