<strong>Operating</strong> the Controls<br />

6.3.10.1 Installer (+) Parameter List<br />

The following values will be displayed <strong>and</strong> can be changed. Values with the symbol<br />

cannot be changed!<br />

Index Parameter Description Area<br />

1 CH Slope<br />

2<br />

CH Anticycle<br />

Time<br />

3 CH Kp<br />

4 CH Ki<br />

5 DHW Kp<br />

6 DHW Ki<br />

7<br />

Ignition<br />

Level<br />

8 Fan Kp<br />

9 Fan Ki<br />

11 CH set-point<br />

12<br />

13<br />

14<br />

CH Pump<br />

Overrun<br />

DHW setpoint<br />

CH max. capacity<br />

Central factor for the ascent/descent<br />

of the edge; defines the temperature<br />

rise in the warm-up<br />

cycle of the central heating dem<strong>and</strong><br />

Central heater anti-cycling time.<br />

During this period the CVBC will<br />

not accept any further central<br />

heating dem<strong>and</strong>s.<br />

Proportional control factor central<br />

heater<br />

Integral control factor central<br />

heater<br />

Proportional control factor for the<br />

drinking-water heater<br />

Integral control factor for the<br />

drinking-water heater<br />

Ignition level with which the boiler<br />

is ignited<br />

Proportional control factor for the<br />

fan controller<br />

Integral control factor for the fan<br />

controller<br />

The actual set-point of the<br />

central heater<br />

Pump overrun time for the central<br />

heater<br />

The actual set-point of the drinking-water<br />

heater<br />

The maximum capacity of the<br />

central heater<br />

- 34 -<br />

Default<br />

V1042 Esys2042<br />

0-60 °C/Min. 5 °C/Min 5 °C/Min<br />

0-900 sec. 90 Sec. 2 min.<br />

0-255 3 3<br />

0-255 95 95<br />

0-255 5 5<br />

0-255 95 95<br />

30-100 % 50% 33%<br />

0-255 13 13<br />

0-255 150 150<br />

30-80 °C 80 °C 70 °C<br />

1-20 Min. 7 Min. 7 Min.<br />

35-65 °C 60 °C 55 °C<br />

60-100% 90% 87%<br />

Gebr. Bruns GmbH is not responsible for typographical errors or technical inaccuracies <strong>and</strong> reserves the right to make adjustments.<br />

Gebr. Bruns GmbH • Hauptstraße 200 • 26683 Saterl<strong>and</strong> •Tel.: + 49 (0) 44 92 / 92 46-0 • Fax: + 49 (0) 44 92 / 71 41<br />

www.bruns-heiztechnik.de • info@bruns-heiztechnik.de