Malfunctions <strong>and</strong> Errors<br />

Code Description Solution<br />

37 Water pressure is too low.<br />

41<br />

43<br />

44<br />

47<br />

Water pressure signal time out. The water<br />

pressure value is not being refreshed often<br />

enough.<br />

Central heating- return flow sensor is not<br />

within normal parameters (short circuit). If<br />

the NTC-sensor is not within normal parameters<br />

<strong>and</strong> remains in this state for longer<br />

than 10 sec., a warning will be displayed. If<br />

the sensor returns to normal parameters,<br />

the warning disappears. The warning<br />

causes the system to shut down. Heating<br />

dem<strong>and</strong>s are deactivated.<br />

Refill water (1.6 bar). Check the water pressure<br />

on the display <strong>and</strong> match it with the pressure<br />

gauge. If the difference is larger than 0.6 bar, replace<br />

the water pressure sensor.<br />

Remove the water pressure sensor <strong>and</strong> make<br />

sure the opening for the sensor is clear of obstructions.<br />

Clean as needed <strong>and</strong> install a filter in<br />

the heating circuit beneath the boiler.<br />

Check the water pressure sensor connection <strong>and</strong><br />

replace the universal sensor as needed.<br />

Check the return flow sensor <strong>and</strong> replace as<br />

needed.<br />

Central heating- return flow sensor is not<br />

within normal parameters (line error). If the<br />

NTC-sensor is not within normal parameters<br />

<strong>and</strong> remains in this state for longer than<br />

Check the return flow sensor <strong>and</strong> replace as<br />

10 sec., a warning will be displayed. If the<br />

needed.<br />

sensor returns to normal parameters, the<br />

warning disappears. The warning causes<br />

the system to shut down. Heating dem<strong>and</strong>s<br />

are deactivated.<br />

Combination error. Either the water pressure<br />

sensor or the supply sensor is defective<br />

or the cable has been interrupted.<br />

Check the universal sensor (water pressure <strong>and</strong><br />

supply sensors against the automatic firing<br />

device.<br />

All errors are recorded in the error log <strong>and</strong> organised in relation to the number of operation<br />

modes. The error codes 10-22 are not visible (they are part of the safety<br />

core).<br />

- 38 -<br />

Gebr. Bruns GmbH is not responsible for typographical errors or technical inaccuracies <strong>and</strong> reserves the right to make adjustments.<br />

Gebr. Bruns GmbH • Hauptstraße 200 • 26683 Saterl<strong>and</strong> •Tel.: + 49 (0) 44 92 / 92 46-0 • Fax: + 49 (0) 44 92 / 71 41<br />

www.bruns-heiztechnik.de • info@bruns-heiztechnik.de