Malfunctions <strong>and</strong> Errors<br />

7.2.2 Locking Codes<br />

The boiler controller also recognises errors that may lead to the heating dem<strong>and</strong><br />

lockup, but does not recognise errors that may lead to a shutdown. If the error is resolved,<br />

it disappears, but will be recorded in the error log. The descriptions of these<br />

codes are as following:<br />

Code Description Solution<br />

30<br />

31<br />

32<br />

33<br />

34<br />

35<br />

Central heating sensor is not within normal<br />

parameters (short circuit). If the NTCsensor<br />

is not within normal parameters <strong>and</strong><br />

remains in this state for longer than 10 sec.,<br />

Check the supply sensor <strong>and</strong> replace the univer­<br />

a warning will be displayed. If the sensor<br />

sal sensor as needed.<br />

returns to normal parameters, the warning<br />

disappears. The warning causes the system<br />

to shut down. Heating dem<strong>and</strong>s are<br />

deactivated.<br />

Central heating sensor is not within normal<br />

parameters (line error). If the NTC-sensor is<br />

not within normal parameters <strong>and</strong> remains<br />

in this state for longer than 10 sec., a warn­<br />

Check the supply sensor <strong>and</strong> replace the univering<br />

will be displayed. If the sensor returns<br />

sal sensor as needed.<br />

to normal parameters, the warning disappears.<br />

The warning causes the system to<br />

shut down. Heating dem<strong>and</strong>s are deactivated.<br />

Domestic warm water sensor is not within<br />

normal parameters (short circuit). If the<br />

NTC-sensor is not within normal parameters<br />

<strong>and</strong> remains in this state for longer than Check the reservoir sensor. If no reservoir<br />

10 sec., a warning will be displayed. If the sensor is connected, check the resistance on the<br />

sensor returns to normal parameters, the end plate <strong>and</strong> replace as needed.<br />

warning disappears. The warning causes<br />

the system to shut down. Heating dem<strong>and</strong>s<br />

are deactivated.<br />

Domestic warm water sensor is not within<br />

normal parameters (line error). If the NTCsensor<br />

is not within normal parameters <strong>and</strong><br />

remains in this state for longer than 10 sec., Check the reservoir sensor. If no reservoir<br />

a warning will be displayed. If the sensor sensor is connected, check the resistance on the<br />

returns to normal parameters, the warning end plate <strong>and</strong> replace as needed.<br />

disappears. The warning causes the system<br />

to shut down. Heating dem<strong>and</strong>s are<br />

deactivated.<br />

This error is caused by the electrical supply<br />

being too low (less than 185 V alternating<br />

current).<br />

The power frequency shows a deviation of<br />

more than +/- 5 %.<br />

- 37 -<br />

Check the electrical current. If the electrical supply<br />

returns to normal, the error will disappear<br />

within 10 sec.<br />

Check the power frequency. If the power frequency<br />

returns to normal, the error will disappear.<br />

Gebr. Bruns GmbH is not responsible for typographical errors or technical inaccuracies <strong>and</strong> reserves the right to make adjustments.<br />

Gebr. Bruns GmbH • Hauptstraße 200 • 26683 Saterl<strong>and</strong> •Tel.: + 49 (0) 44 92 / 92 46-0 • Fax: + 49 (0) 44 92 / 71 41<br />

www.bruns-heiztechnik.de • info@bruns-heiztechnik.de