forming droplets, these drip into the fire or run out on the floor.<br />

This is common at the time of startup after installation, during<br />

periods of time when incoming water is very cold, or the heater<br />

may be undersized for the requirements.<br />

Droplets from the bottom of the flue may be due to corrosive<br />

combustion products or improper vent. Check <strong>with</strong> your dealer<br />

for more information.<br />

16<br />

CATHODIC PROTECTION - ANODE (FIG. 1)<br />

The anode rod <strong>with</strong>in the tank is designed to be slowly consumed<br />

cathodically, minimizing corrosion in the glass lined tank. A<br />

hydrogen sulfide (rotten egg) odor may result if water contains<br />

high sulfate and/or minerals. Chlorinating the water supply should<br />

minimize the problem. (See EXTENDED NON-USE PERIODS).<br />

NOTE: Anode must remain installed (except for inspection) to<br />

avoid shortening tank life. See LIMITED WARRANTY. Replace<br />

as necessary.<br />

WARNING: DO NOT BY-PASS ANY CONTROLS TO MAKE HEATER OPERATE.<br />

OPERATE ONLY AS WIRED FROM FACTORY.<br />

TROUBLE SHOOTING<br />

Please check guidelines below. For your safety, water heater service should be performed only by a qualified service technician.<br />

Read the GENERAL SAFETY INFORMATION section first.<br />

PROBLEM LED STATUS CAUSE SOLUTION<br />

Check for power to heater.<br />

Off No power to system control. Check wiring harness for proper connections.<br />

Check for line voltage at harness connectors.<br />

Slow Blink<br />

Bright-Dim Normal operation Not applicable.<br />

1 Flash Setpoint error, internal failure detected. Replace gas control valve.<br />

Replace pressure switch.<br />

Replace pressure switch.<br />

2 Flashes Pressure switch failed to open. Replace blower assembly.<br />

Replace pressure switch.<br />

3 Flashes Pressure switch failed to close. Replace blower assembly.<br />

ECO activated. Replace ECO.<br />

4 Flashes Blower Assembly is energized. Replace gas control valve.<br />

Internal hardware failure. Replace gas control valve.<br />

Insure that burner stays lit.<br />

GAS Flame signal sensed out of sequence. Insure that igniter wires are not loose at gas valve.<br />

VALVE Replace gas control valve.<br />

Insure that burner stays lit.<br />

Blower Assembly is energized. Insure that igniter wires are not loose at gas valve.<br />

Replace gas control valve.<br />

<strong>Gas</strong> supply is off or too low to operate.<br />

Damaged or broken HSI element.<br />

Appliance not properly earth ground.<br />

Flame sense rod contaminated or not positioned<br />

correctly.<br />

6 Flashes System lockout. HSI element not positioned correctly.<br />

HSI element or flame sense rod wiring not<br />

connected properly.<br />

Less than 100Vac between flame rod and burner<br />

pan <strong>with</strong> 120Vac input to control.<br />

Cycle external power or remove request for heat<br />

for 2 seconds before reapplying.<br />

Water temperature is below 36°F. Wait until gas control generates a self-reset.<br />

Rapidly Loose connection between valve Make sure connections<br />

blinking and spud assembly. are properly seated.<br />

Internal component failure. Replace gas control valve.