26<br />
Commissioning without heat pump<br />
The indoor module can be run without heat pump, as<br />
only an electric boiler, to produce heat and hot water,<br />
for example before the heat pump is installed.<br />
Connect the pipe for docking in from the heat pump<br />
(XL8) with the pipe out from the heat pump (XL9).<br />
Enter menu 5.2.4 System settings and deactivate the heat<br />
pump.<br />
NOTE<br />
Select operating mode auto or <strong>manual</strong> when<br />
the indoor module is to run with the heat pump.<br />
Pump speed<br />
Both the circulation pumps in VVM 500 are frequency<br />
controlled and set themselves using control and external<br />
heating requirement. In the menu there are two operating<br />
modes for the circulation pumps, continuous and auto.<br />
If auto is selected the circulation pumps are controlled<br />
automatically by heating and hot water demands.<br />
��������<br />
Tillgängligt tryck<br />
����� (Pa)<br />
70<br />
60<br />
50<br />
40<br />
30<br />
20<br />
10<br />
LEK<br />
�������� ����������� ����<br />
��������� ��������� ����������� ����� ���<br />
25%<br />
0<br />
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8<br />
Luftflöde ���� ����� (l/s)<br />
Chapter 6 | Commissioning and adjusting<br />
100%<br />
��������<br />
Tillgängligt tryck<br />
����� (Pa)<br />
70<br />
60<br />
50<br />
40<br />
30<br />
20<br />
10<br />
�������� ����������� ����<br />
��������� ��������� ������ ����� ����<br />
25%<br />
0<br />
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8<br />
Luftflöde ���� ����� (l/s)<br />
100%<br />
Post-adjustment, venting<br />
Air is initially released from the hot water and venting<br />
may be necessary. If gurgling sounds can be heard from<br />
the climate system, the entire system will require additional<br />
venting. Vent the installation through the venting valves<br />
(QM20). When venting, VVM 500 must be off.<br />
NIBE VVM 500