Residenziali Aria-Acqua / Residential Air-Water<br />

refrigeratori e Pompe di calore Aria-Acqua Air cooled water chillers and heat pumps refrigerant R410A<br />

EH<br />

Residential - technical data Air-Water heat pumps<br />

Code 07241010 07241020 07241030 07241040 07241050 07241060<br />

Price Euro € 5.131,00 5.472,00 6.222,00 5.790,00 6.878,00 6.446,00<br />

Models Eh Rif. 0510 MS 0710 MS 0910 MS 0910 T 1110 MS 1110 T<br />

APPLICAtION WIth tERMINAL AIR uNItS<br />

Nom<strong>in</strong>al cool<strong>in</strong>g capacity 1 kW 5,50 6,90 8,80 8,80 10,8 11,1<br />

E.E.R. (*) 1 2,74 2,63 2,66 2,66 2,62 2,62<br />

Absorbed power (*) 1 kW 2,00 2,62 3,32 3,32 4,12 4,25<br />

Nom<strong>in</strong>al current (*) 1 A 9,4 12,1 16,4 4,8 20,2 6,5<br />

Exchanger water nom<strong>in</strong>al flow rate 1 l/h 946 1187 1514 1514 1858 1909<br />

Useful pressure head for electric pump 1 kPa 55 55 79 79 72 72<br />

Sound power 1 dB(A) 68 69 69 69 69 69<br />

Sound pressure 1 dB(A) 46 47 47 47 47 47<br />

Nom<strong>in</strong>al heat<strong>in</strong>g capacity 3 kW 5,8 7,43 9,46 9,46 11,52 11,97<br />

COP 3 2,72 2,65 2,76 2,76 2,51 2,6<br />

Absorbed power (*) 3 kW 2,13 2,80 3,43 3,43 4,6 4,59<br />

Nom<strong>in</strong>al current (*) 3 A 9,9 12,3 16,4 4,8 20,2 6,6<br />

APPLICAtION WIth RADIANt PANELS<br />

Nom<strong>in</strong>al cool<strong>in</strong>g capacity 2 kW 7,50 8,90 12,10 12,10 14,5 14,8<br />

E.E.R. (*) 2 3,71 3,27 3,53 3,53 3,2 3,27<br />

ESEER 1 3,15 2,77 3,16 3,16 3,11 3,15<br />

Absorbed power (*) 2 kW 2,02 2,72 3,43 3,43 4,53 4,53<br />

Nom<strong>in</strong>al current (*) 2 A 9,8 12,6 16,8 5,3 21 7,2<br />

Nom<strong>in</strong>al heat<strong>in</strong>g capacity 4 kW 5,95 7,76 9,54 9,54 12,06 12,47<br />

COP (**) 4 3,40 3,59 3,43 3,43 3,48 3,59<br />

Absorbed total power 4 kW 1,75 2,16 2,78 2,78 3,47 3,47<br />

Nom<strong>in</strong>al current (*) 4 A 10,3 12,8 16,8 5,3 21 7,3<br />

Sound power 4 dB(A) 70 72 72 72 72 72<br />

Heat power 7 kW 3,61 4,66 5,93 5,93 7,46 7,44<br />

COP 7 2,10 2,12 2,10 2,10 2,13 2,11<br />

Absorbed power 7 kW 1,72 2,22 2,82 2,82 3,5 3,52<br />

Electrical power V-ph-Hz 230-1-50 400-3+N-50 230-1-50 400-3+N-50<br />

Maximum current A 15,3 19,9 24,7 10,0 31,2 12,8<br />

Start<strong>in</strong>g current A 26 34 40 48 45 64<br />

Electric pump absorbed power kW 0,18 0,18 0,29 0,29 0,29 0,29<br />

Electric pump absorbed current A 1,12 1,40<br />

Fan n° 1 2<br />

Scroll / Step compressor n° 1/1<br />

Exchanger water content l 0,34 0,45 0,58 0,58 0,76 0,76<br />

Inertial storage content l 19 30<br />

Shipp<strong>in</strong>g weight kg 141 143 167 167 176 176<br />

Water fitt<strong>in</strong>gs Ø 1”G<br />

Dimensions<br />

Width (L) mm 990<br />

Height (H) mm 905 1290<br />

Depth (P) mm 380<br />

(1) Data referred to the follow<strong>in</strong>g conditions: water 12/7 °C and outdoor temperature 35 °C.<br />

(2) Data referred to the follow<strong>in</strong>g conditions: water 23/18 °C and outdoor temperature 35 °C.<br />

(3) Data referred to the follow<strong>in</strong>g conditions: water 40/45 °C and outdoor temperature: 7 °C C.S.<br />

(4) Data referred to the follow<strong>in</strong>g conditions: <strong>in</strong>ternal exchanger water 30/35 °C, outdoor temperature: 7 °C C.S. / 6°C B.U.<br />

(7) Data referred to the follow<strong>in</strong>g conditions: <strong>in</strong>ternal exchanger water outlet 35 °C and flow rate as <strong>in</strong> condition (4), outdoor temperature: -7 °C B.S.<br />

Notes:<br />

Sound pressure level <strong>in</strong> dB(A) referred to a distance of 5 m from the unit with a directional factor equal to 2.<br />

Sound power level <strong>in</strong> dB(A) based on measurements taken <strong>in</strong> compliance with the standards UNI EN-ISO 3744 and Eurovent 8/1.<br />

E.S.E.E.R. (European Seasonal EER) European average seasonal yield.<br />

(*) Without electric pump.<br />

(**) Reference for the French market tax credit (accord<strong>in</strong>g to EN14511 14511).<br />

H<br />

H<br />

Operat<strong>in</strong>g limits Heat<strong>in</strong>g mode Cool<strong>in</strong>g mode<br />

Outdoor air temperature -15 ÷ 40 °C -10 ÷ 43 °C<br />

Exchanger outlet water temp. 30÷53 °C (air >7 °C) 4 ÷ 20 °C<br />

Max exchanger <strong>in</strong>let water temp. 47 °C 25 °C<br />

Temperature drop on the evaporator 3 ÷ 8 °C.<br />

Water pressure: m<strong>in</strong>imum 0.5 Barg - maximum 3 Barg.<br />

P<br />

L<br />

P<br />

L<br />