Made in Japan
Made in Japan
Made in Japan
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Industriali Aria-Acqua / Industrial Air-Water<br />
refrigeratori e Pompe di calore Aria-Acqua Air cooled water chillers and heat pumps refrigerant R410A<br />
EH<br />
Industrial - technical data Air-Water heat pumps<br />
Modelli a richiesta (disponibilità circa 40 giorni dalla conferma dell’ord<strong>in</strong>e)<br />
Models on request (available <strong>in</strong> about 40 days from the order confirmation)<br />
Code 07241410 07241420 07241430 07241440 07241450 07241460 07241470<br />
Price Euro € 31.591,00 36.780,00 39.424,00 40.453,00 44.138,00 49.151,00 52.395,00<br />
Models Eh Rif. 7010 2CI 8810 2CI 10110 2CI 11410 2CI 12610 2CI 14310 2CI 15110 2CI<br />
APPLICAtION WIth tERMINAL AIR uNItS<br />
Nom<strong>in</strong>al cool<strong>in</strong>g capacity 1 kW 69,4 85,2 99,3 107,2 118,5 135,6 150,2<br />
E.E.R. (*) 1 2,92 2,84 2,85 2,61 2,62 2,58 2,55<br />
ESEER 4,19 4,22 4,19 3,86 3,83 3,83 3,78<br />
Absorbed power (*) 1 kW 23,8 30 34,9 41 45,3 52,6 58,9<br />
Nom<strong>in</strong>al current (*) 1 A 43,9 51,3 62,7 72,7 79,7 90,6 102,6<br />
Exchanger water nom<strong>in</strong>al flow rate 1 l/h 11937 14654 17080 18438 20382 23323 25834<br />
Useful pressure head for electric pump 1 kPa 150 140 130 130 115 165 155<br />
Sound power 1 dB(A) 74 75 76 81 81 82 82<br />
Sound pressure 1 dB(A) 53 54 55 57 57 58 58<br />
Nom<strong>in</strong>al heat<strong>in</strong>g capacity 3 kW 79 96 111 120 135 154 170<br />
COP 3 3,36 3,29 3,34 3,22 3,31 3,25 3,21<br />
Absorbed power (*) 3 kW 23,5 29,2 33,2 37,3 40,8 47,4 53<br />
Nom<strong>in</strong>al current (*) 3 A 43,4 50 59,6 66,2 71,8 81,4 92,4<br />
Electrical power V-ph-Hz 400-3+N-50<br />
Maximum current A 63,1 74 84 86,5 95,5 111 122<br />
Start<strong>in</strong>g current A 203,5 259,5 308,5 311 319 358 372<br />
Electric pump absorbed power kW 1,1 1,5 1,5 1,5 1,5 2,2 2,2<br />
Electric pump absorbed current A 2,6 3,5 3,5 3,5 3,5 5 5<br />
Fan n° 6 8 10 4 4 6 6<br />
Scroll / Step compressor n° 2/3 2/3 2/3 2/3 2/2 2/3 2/2<br />
Exchanger water content l 6,9 8,4 9,9 11,1 12,6 14,9 17,4<br />
Inertial storage content l 250 450<br />
Shipp<strong>in</strong>g weight kg 1055 1220 1290 1430 1562 1605 1680<br />
Water fitt<strong>in</strong>gs Ø 2"<br />
Dimensions<br />
Width (L) mm 3150 3250<br />
Height (H) mm 1520 2000<br />
Depth (P) mm 1210 1520<br />
(1) Data referred to the follow<strong>in</strong>g conditions: water 12/7 °C and outdoor temperature 35 °C.<br />
(3) Data referred to the follow<strong>in</strong>g conditions: water 40/45 °C and outdoor temperature: 7 °C B. S.<br />
Notes:<br />
Sound pressure level <strong>in</strong> dB(A) referred to a distance of 5 m from the unit with a directional<br />
factor equal to 2.<br />
Sound power level <strong>in</strong> dB(A) based on measurements taken <strong>in</strong> compliance with the standards<br />
UNI EN-ISO 3744 and Eurovent 8/1.<br />
E.S.E.E.R. (European Seasonal EER) European average seasonal yield.<br />
(*) Without electric pump<br />
H<br />
P<br />
L<br />
Operat<strong>in</strong>g limits Heat<strong>in</strong>g mode Cool<strong>in</strong>g mode<br />
Outdoor air temperature -10 ÷ 40 °C 10 ÷ 43 °C<br />
Exchanger outlet water temp. 37÷53 °C (air >6 °C) 5 ÷ 15 °C<br />
Max exchanger <strong>in</strong>let water temp. 47 °C 20 °C<br />
Temperature drop on the evaporator 3 ÷ 8 °C.<br />
Water pressure: m<strong>in</strong>imum 0.5 Barg - maximum 6 Barg.<br />
131