6-6 Creating and Running the Example Application Program<br />
Publication <strong>1747</strong>-<strong>6.5.5</strong> - August 2000<br />
Downloading and Running the Program via an Ethernet Network<br />
IMPORTANT<br />
To communicate with your <strong>SL</strong>C 5/05 processor over<br />
an Ethernet network you must first configure the<br />
processor’s Ethernet communications channel and<br />
assign it a unique IP address. See Appendix B for<br />
information on configuring the Ethernet<br />
communications channel.<br />
Follow the procedure below to download and run the example<br />
program via an Ethernet network.<br />
1. Click on the R<strong>SL</strong>ogix <strong>500</strong> Communications menu and select<br />
System Comms.<br />
2. The Communications window will open (Your window may look<br />
different depending upon the drivers you have installed):<br />
3. Select the “+” next to your Ethernet driver (AB-ETH-1 above) to<br />
expand the tree.<br />
4. Highlight the <strong>SL</strong>C <strong>500</strong> processor as shown above and click on the<br />
Download button.<br />
5. After the download is complete, change the <strong>SL</strong>C <strong>500</strong> processor<br />
mode to Run.