7.3 VSD SCREEN<br />

The 'VSD SCREEN' shows the motor current as a<br />

percentage of full load amps (FLA), the current limit<br />

setpoint (set locally (refer to 'LOCAL MOTOR<br />

CURRENT LIMIT') or remotely by an analogue signal:<br />

(0-20 mA, 4-20 mA, 0-10 Vdc or 2-10 Vdc) in the<br />

analogue remote mode, or PWM signal in digital remote<br />

mode or via the ISN/GPIC interface in the ISN mode)<br />

and the pulldown demand time remaining, when<br />

pulldown demand limiting is active.<br />

The screen also displays the output voltage, frequency<br />

and phase current to the motor, total and cumulative<br />

input Kilowatts and PRV position. In addition, supply<br />

kVA, power factor and voltage and current total<br />

harmonic distortion are shown on models with harmonic<br />

filters.<br />

The 'LOCAL MOTOR CURRENT LIMIT' and<br />

'PULLDOWN DEMAND LIMIT' and 'TIME' are also<br />

programmed on this screen:<br />

Local Motor Current Limit<br />

Defines the maximum allowable motor current during<br />

operation as a percentage of FLA. When the motor<br />

current reaches or exceeds the programmed limit the<br />

PRV are prohibited from opening or closed to reduce the<br />

motor current.<br />

Pulldown Demand Limit<br />

Defines the maximum allowable motor current during<br />

pulldown demand limiting at unit startup as a<br />

percentage of FLA. This value overrides the 'LOCAL<br />

MOTOR CURRENT LIMIT' for the time specified in the<br />

motor current 'PULLDOWN DEMAND TIME'.<br />

Pulldown Demand Time<br />

Specifies the period of time that pulldown demand<br />

limiting will be active during unit startup.<br />

VSD Details - see Section 7.3.1<br />

160-54-OI-GB0 13<br />

ACC Details - Service Technicians<br />

Filter Inhibit and Filter Details - Units with Harmonic<br />

Filters<br />