16 160-54-OI-GB0<br />
Cycling Offset - Shutdown<br />
Defines the leaving chilled liquid temperature at which<br />
the unit will shutdown on a 'LEAVING CHILLED <strong>LIQUID</strong><br />
- LOW TEMPERATURE'. The 'OFFSET' (below<br />
'SETPOINT') can be programmed between 0.56°C<br />
(1°F) and 35.6°C (64°F) to a minimum cut-out of 2.2°C<br />
(36°F) for water cooling applications (1.1°C (34°F) with<br />
Smart Freeze enabled) or -14.4°C (6°F) for brine/glycol<br />
applications.<br />
When the programmed leaving chilled liquid<br />
temperature 'SETPOINT' is changed, the shutdown is<br />
fixed at of 2.2°C (36°F) for water cooling applications<br />
(1.1°C (34°F) with Smart Freeze enabled) or -14.4°C<br />
(6°F) for brine/glycol applications for the next ten<br />
minutes.<br />
The shutdown will then revert to the 'SETPOINT' plus<br />
the 'OFFSET' after ten minutes has elapsed.<br />
Cycling Offset - Restart<br />
Defines the leaving chilled liquid temperature at which<br />
the unit will restart after a 'LEAVING CHILLED <strong>LIQUID</strong> -<br />
LOW TEMPERATURE ' shutdown. The 'OFFSET'<br />
(above 'SETPOINT') can be programmed between 0°C<br />
(0°F) and 21.1°C (70°F) to a maximum restart of 26.7°C<br />
(80°F). This 'OFFSET' can be used to reduce unit<br />
cycling by delaying the restart until the cooling load has<br />
increased dramatically.<br />
Local Motor Current Limit<br />
Defines the maximum allowable motor current during<br />
operation as a percentage of FLA. When the motor<br />
current reaches or exceeds the programmed limit the<br />
PRV are prohibited from opening or closed to reduce the<br />
motor current.<br />
Pulldown Demand Limit<br />
Defines the maximum allowable motor current during<br />
pulldown demand limiting at unit startup as a<br />
percentage of FLA. This value overrides the 'LOCAL<br />
MOTOR CURRENT LIMIT' for the time specified in the<br />
motor current 'PULLDOWN DEMAND TIME'.<br />
Pulldown Demand Time<br />
Specifies the period of time that pulldown demand<br />
limiting will be active during unit startup.<br />
Remote Analog Input Range<br />
(Flash Memory Card version C.MLM.01.01 or later)<br />
Defines the signal range applied for remote reset of the<br />
leaving 'Chilled Liquid Temperature Setpoint' and<br />
'Current Limit Setpoint' in the analogue remote mode.<br />
The value should be programmed for 0-10Vdc if the<br />
remote signal is 0-10 Vdc or 0-20 mA. If the remote<br />
signal is 2-10 Vdc or 4-20 mA, the value must be<br />
programmed for 2-10 Vdc.